Fig. 11 -- Interface Fan Board (IFB)

SINGLE SPEED COOLING WITH HIGHER

ELECTRIC HEAT SPEED

This unit can also be configured to operate with single speed

cooling and a higher speed for an accessory electric heater.

1. Using Fig. 11, move the two pin DEHUM jumper from the

“STD” position to the “DEHUM” position.

2. See Table 2 for minimum airflow for electric heat operation.

Add electric heater and filter pressure drop to duct system

static pressure to determine total external static pressure.

3. Select speed tap from Table 4 that will achieve required

airflow from Table 2.

4. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 3 for color coding).

5. Connect the desired speed tap wire to the “HIGH” terminal

on the interface fan board (IFB).

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit component

damage or improper operation.
To use this mode, a speed connection must be made on the

“HIGH” terminal that meets or exceeds the minimum

airflow found in Table 2.

!

CAUTION

Table 3 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med--High Speed

Red = Med Speed

Pink = Med--Low Speed

Blue = Low Speed

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Disconnect electrical power to the unit and install lockout

tag before changing blower speed.

!

WARNING

CONTINUOUS FAN OPERATION

When the DEHUM feature is not used, the continuous fan speed

will be the same as cooling fan speed. When the DEHUM feature

is used, the continuous fan will operate on IFB “LOW” speed
when the DH control lead is not energized, or IFB “HIGH” speed

when the DH lead is energized (see Fig. 11).

COOLING SEQUENCE OF OPERATION

With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in the AUTO position, the cooling sequence of

operation is as follows:
When the room temperature rises to a point that is slightly above

the cooling control setting of the thermostat, the thermostat

completes the circuit between thermostat terminal R to terminals Y
and G. These completed circuits through the thermostat connect

contactor coil (C) (through unit wire Y) and time delay relay
(TDR) (through unit wire G) across the 24--V secondary of

transformer (TRAN).
The normally open contacts of energized contactor (C) close and

complete the circuit through compressor motor (COMP) to

condenser (outdoor) fan motor (OFM). Both motors start instantly.
A set of normally open contacts on the interface fan board (IFB)

are closed which energizes a circuit to the indoor fan motor (IFB).
NOTE: Once the compressor has started and then has stopped, it
should not be started again until 5 minutes have elapsed.
The cooling cycle remains on until the room temperature drops to a

point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat breaks the circuit between

thermostat terminal R to terminals Y and G. These open circuits
deenergize contactor coil C and IFB. The condenser and

compressor motors stop. After a 90--second delay, the blower

motor stops. The unit is in a standby condition, waiting for the next
call for cooling from the room thermostat.