Warning, Pre--start--up, Start--up – Carrier 50VL---A User Manual

Page 12

Advertising
background image

12

PRE--START--UP

ENVIRONMENTAL,

FIRE,

EXPLOSION,

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death and/or property damage.

1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Relieve and recover all refrigerant from system before

touching or disturbing compressor plug if refrigerant
leak is suspected around compressor terminals.

3. Never attempt to repair soldered connection while

refrigerant system is under pressure.

4. Do not use torch to remove any component. System

contains oil and refrigerant under pressure.

5. To remove a component, wear protective goggles and

proceed as follows:

a. Shut off electrical power to unit and install

lockout tag.

b. Relieve and reclaim all refrigerant from system

using both high-- and low--pressure ports.

c. Cut component connecting tubing with tubing

cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to torch

flame.

!

WARNING

Proceed as follows to inspect and prepare the unit for initial

start--up:

1. Remove all access panels (see Fig. 17).
2. Read and follow instructions on all DANGER, WARNING,

CAUTION, and INFORMATION labels attached to, or

shipped with unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages, such as

broken lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and

on unit base. Detecting oil generally indicates a
refrigerant leak. Leak test all refrigerant tubing

connections using electronic leak detector, or
liquid--soap solution. If a refrigerant leak is detected, see
following Check for Refrigerant Leaks section.

c. Inspect all field-- and factory--wiring connections. Be

sure that connections are completed and tight.

d. Ensure wires do not touch refrigerant tubing or sharp

sheet metal edges.

e. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that condensate drain pan and trap are filled

with water to ensure proper drainage.

b. Make sure that all tools and miscellaneous loose parts

have been removed.

START--UP

Step 1 — Check for Refrigerant Leaks

Proceed as follows to locate and repair a refrigerant leak and to

charge the unit:

1. Locate leak and make sure that refrigerant system pressure

has been relieved and reclaimed from both high-- and
low--pressure ports.

2. Repair leak following accepted practices.

NOTE: Install a filter drier whenever the system has been opened
for repair.

3. Add a small charge of Puron (R--410A) refrigerant vapor to

system and leak--test unit.

4. Recover refrigerant from system and evacuate to 500

microns if no additional leaks are found.

5. Charge unit with Puron (R--410A) refrigerant, using an

accurate scale. Refer to unit rating plate for required charge.

Step 2 — Start--Up Cooling Section And Make

Adjustments

Complete the required procedures given in the Pre--Start--Up

section before starting the unit. Do not jumper any safety devices

when operating the unit. Do not operate the unit when the outdoor
temperature is below 40°F (4°C) (unless accessory low--ambient

kit is installed). Do not rapid cycle the compressor. Allow 5
minutes between “on” cycles to prevent compressor damage.

CHECKING COOLING CONTROL OPERATION

Start and check the unit for proper cooling control operation as

follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is
placed in AUTO position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room

temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that compressor

and outdoor fan shut down when control setting is satisfied
and that indoor blower shuts down after 90 second fan time
delay expires.

IMPORTANT: Three--phase, scroll compressors are direction
oriented. Unit must be checked to ensure proper compressor
3--phase power lead orientation. If not corrected within 5 minutes,
the internal protector will shut off the compressor. The 3--phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures may be minimal.

CHECKING AND ADJUSTING REFRIGERANT

CHARGE

The refrigerant system is fully charged with Puron (R--410A)
refrigerant and is tested and factory sealed.
NOTE:

Adjustment of the refrigerant charge is not required

unless the unit is suspected of not having the proper Puron
(R--410A) charge.
A subcooling charging chart is attached to the inside of the
compressor access panel (see Fig. 17). The chart includes the

required liquid line temperature at given discharge line pressures
and outdoor ambient temperatures.
An accurate thermocouple-- or thermistor--type thermometer, and a

gauge manifold are required when using the subcooling charging
method for evaluating the unit charge. Do not use mercury or small

dial--type thermometers because they are not adequate for this type
of measurement.
NOTE: Allow system to operate for a minimum of 15 minutes
before checking or adjusting refrigerant charge.
IMPORTANT:

When evaluating the refrigerant charge, an

indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.

50V

L

--

A

Advertising