Warning, Step 6 — connect condensate drain, Step 7 — install duct connections – Carrier 50VL---A User Manual

Page 8

Advertising
background image

8

Step 6 — Connect Condensate Drain

NOTE: When installing condensate drain connection be sure to
comply with local codes and restrictions.
Model 50VL--A disposes of condensate water through a 3/4 in.

NPT fitting which exits through the base on the evaporator coil

access side. See Fig. 2 and 3 for location.
Condensate water can be drained directly onto the roof in rooftop

installations (where permitted) or onto a gravel apron in ground
level installations. Install a field--supplied 2--in. (51 mm)

condensate trap at end of condensate connection to ensure proper

drainage. Make sure that the outlet of the trap is at least 1 in. (25
mm) lower than the drain pan condensate connection to prevent the

pan from overflowing (See Fig. 8). When using a gravel apron,
make sure it slopes away from the unit.
Connect a drain tube using a minimum of 3/4 --in. PVC or 3/4 --in.
copper pipe (all field--supplied) at the outlet end of the 2--in. (51

mm) trap. Do not undersize the tube. Pitch the drain tube

downward at a slope of at least 1--in. (25 mm) for every 10 ft (3.1
m) of horizontal run. Be sure to check the drain tube for leaks.

Prime trap at the beginning of the cooling season start--up.

TRAP
OUTLET

1-in. (25 mm) min.

2-in. (51 mm) min.

A09052

Fig. 8 -- Condensate Trap

Step 7 — Install Duct Connections

The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of

non--residence type air conditioning and ventilating systems,

NFPA 90A or residence type, NFPA 90B and/or local codes and
ordinances.
Select and size ductwork, supply--air registers, and return air grilles
according to ASHRAE (American Society of Heating,

Refrigeration, and Air Conditioning Engineers) recommendations.
The unit has duct flanges on the supply-- and return--air openings

on the side of the unit.
When designing and installing ductwork, consider the following:

1. All units should have field--supplied filters or accessory

filter rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.

2. Avoid abrupt duct size increases and reductions. Abrupt

change in duct size adversely affects air performance.

IMPORTANT: Use flexible connectors between ductwork and
unit to prevent transmission of vibration. Use suitable gaskets to
ensure weather--tight and airtight seal. When electric heat is
installed, use fireproof canvas (or similar heat resistant material)
connector between ductwork and unit discharge connection. If
flexible duct is used, insert a sheet metal sleeve inside duct. Heat
resistant duct connector (or sheet metal sleeve) must extend 24--in.
(610 mm) from electric heater element.

3. Size ductwork for cooling air quantity (cfm). The minimum

air quantity for proper electric heater operation is listed in

Table 2. Heater limit switches may trip at air quantities
below those recommended.

4. Seal, insulate, and weatherproof all external ductwork. Seal,

insulate and cover with a vapor barrier all ductwork passing
through conditioned spaces. Follow latest Sheet Metal and

Air Conditioning

Contractors

National Association

(SMACNA) and Air Conditioning Contractors Association

(ACCA) minimum installation standards for residential
heating and air conditioning systems.

5. Secure all ducts to building structure. Flash, weatherproof,

and vibration--isolate duct openings in wall or roof
according to good construction practices.

CONFIGURING UNITS FOR DOWNFLOW

(VERTICAL) DISCHARGE

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before performing service or maintenance operations on the

system, turn off main power to unit and install lockout tag.

!

WARNING

1. Open all electrical disconnects and install lockout tag before

starting any service work.

2. Remove horizontal (metal) ductcovers to access vertical

(downflow) discharge duct knockouts in unit basepan. (See
Fig. 9.)

To remove downflow return and supply knockout covers, break
front and right side connecting tabs with a screwdriver and

hammer. Push cover down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an
electrical knockout. Reinstall horizontal duct covers (Fig. 9)
shipped on unit from factory. Insure openings are air and
watertight.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:

1. Units are shipped for side shot installation.

2. Select and size ductwork, supply--air registers, and

return--air grilles according to American Society of Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE)

recommendations.

3. Use flexible transition between rigid ductwork and unit to

prevent transmission of vibration. The transition may be
screwed or bolted to duct flanges. Use suitable gaskets to

ensure weather--tight and airtight seal.

4. All units must have field--supplied filters or accessory filter

rack installed in the return--air side of the unit.

Recommended sizes for filters are shown in Table 1.

5. Size all ductwork for maximum required airflow (either

heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be
affected.

6. Adequately insulate and weatherproof all ductwork located

outdoors. Insulate ducts passing through unconditioned

space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National
Association (SMACNA) and Air Conditioning Contractors

of America (ACCA) minimum installation standards for
heating and air conditioning systems. Secure all ducts to

building structure.

7. Flash, weatherproof, and vibration--isolate all openings in

building structure in accordance with local codes and good
building practices.

50V

L

--

A

Advertising