Troubleshooting, Start--up checklist – Carrier 50VL---A User Manual

Page 27

Advertising
background image

27

readily. POE oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Take all necessary

precautions to avoid exposure of the oil to the atmosphere.

Servicing Systems on Roofs with Synthetic Materials

POE (polyolester) compressor lubricants are known to cause long

term damage to some synthetic roofing materials. Exposure, even if
immediately cleaned up, may cause embrittlement (leading to

cracking) to occur in one year or more. When performing any

service that may risk exposure of compressor oil to the roof, take
appropriate precautions to protect roofing. Procedures which risk

oil leakage include, but are not limited to, compressor replacement,
repairing refrigerant leaks, replacing refrigerant components such

as filter drier, pressure switch, metering device, coil, accumulator,

or reversing valve.

Synthetic Roof Precautionary Procedure

1. Cover extended roof working area with an impermeable

polyethylene (plastic) drip cloth or tarp. Cover an
approximate 10 x 10 ft (3 x 3 m) area.

2. Cover area in front of the unit service panel with a terry

cloth shop towel to absorb lubricant spills, prevent run--offs,
and protect drop cloth from tears caused by tools or

components.

3. Place terry cloth shop towel inside unit immediately under

component(s) to be serviced and prevent lubricant run--offs
through the louvered openings in the unit base.

4. Perform required service.
5. Remove and dispose of any oil contaminated material per

local codes.

Liquid Line Filter Drier

The filter drier is specifically designed to operate with Puron. Use

only factory--authorized components. Filter drier must be replaced
whenever the refrigerant system is opened. When removing a filter

drier, use a tubing cutter to cut the drier from the system. Do not
unsweat a filter drier from the system. Heat from unsweating will

release moisture and contaminants from drier into system.

Puron (R--410A) Refrigerant Charging

Refer to unit information plate and charging chart. Some R--410A
refrigerant cylinders contain a dip tube to allow liquid refrigerant to

flow from cylinder in upright position. For cylinders equipped
with a dip tube, charge Puron units with cylinder in upright

position and a commercial metering device in manifold hose.

Charge refrigerant into suction--line.

TROUBLESHOOTING

Refer to the Troubleshooting Chart (Table 10) for troubleshooting

information.

START--UP CHECKLIST

Use the Start--Up Checklist at the back of this manual.

50V

L

--

A

Advertising