SECT

IO

N

3

3-15

T-268-07

modulation valve (SMV) and suction solenoid valve
(SSV) with the compressor energized.
When pulling down from a control temperature that is
more than 5_C (9_F) above set point, both valves will

be open to reduce the pulldown time unless suction
solenoid override or current limiting is activated. See
section 2.10 for explanation of suction solenoid
override. The current limit function will restrict the
valves if the current is above the selected value. When

the controlling probe temperature reaches set point, the
suction solenoid valve will close.

When the controlling probe temperature enters the

in-range temperature tolerance as selected at function
code Cd30, the in-range light will energize.

The Controller logic is designed so the suction

modulation valve will begin to close as the set point is
reached. The modulation valve will close to restrict
refrigerant flow until the capacity of the unit and the
load are balanced, unless the compressor reliability

enhancement logic on the first compressor start
prevents closure.

If the temperature drops below the set point, the

compressor will remain running for a few minutes. This
is to accommodate any initial undershoot which might
occur. After this time, and at 0.2_C (0.4_F) or greater
below the set point, the compressor will be turned OFF.
The heaters will be energized if the temperature drops to
0.5_C (0.9_F) below the set point. The heaters will
de-energize when the temperature rises to 0.2_C
(0.4_F) below the set point. The compressor will not

restart until the temperature rises to 0.2_C (0.4_F)
above the set point and a three minute time delay since
the last compressor turn off has been satisfied.

b. Operation in the dehumidification mode

(Code 33 value selected) -- Optional

The dehumidification mode is activated by selecting
Code 33, choosing a desired relative humidity value,
and pressing the ENTER key. The control probe LED
(supply 1) will flash ON and OFF every second to
indicate that the dehumidification mode is active. Once

the Mode is active and the following conditions are
satisfied, the Controller will activate the heat relay to
begin dehumidification.
1. The humidity sensor reading is above the set point

and valid (AL67).

2. The pulldown mode is NOT active. (ie., The SSV

valve is closed, and the control temperature is less
than 5_C above set point.)

3. The control probe (i.e.; Supply 1) temperature is

less than set point, plus 0.25_C.

4. Temperature control set point is greater than --10_C

(+14_F), or --5_C (+23_F) optionally, in the
perishable range, and the compressor is running.

5. The heater debounce timer (three minutes) has

timed out.

6. Heater termination thermostat (HTT) is closed.
7. The Controlled Atmosphere (CA) option VENT or

Pre-Trip mode is not initiated.

8. Humidity sensor alarm is not active (AL67).
9. High pressure switch (HPS) is not open.
If the above conditions remain true for at least one hour
the evaporator fans will switch from high to low speed
operation (on units so equipped). The evaporator fan

speed will switch every hour thereafter as long as all
conditions are met (see Bulb Mode section for different
evaporator fan speed options). If any condition except
for item (1.) becomes false OR if the relative humidity
sensed is 2% below the dehumidification set point, the

high speed evaporator fans will be energized.
The dehumidification mode applies power to the defrost
and drain pan heaters. This added heat load causes the
Controller to open the modulating valve to match the

new total heat load while still holding the supply air
temperature very close to the set point.
Opening the modulating valve reduces the temperature
of the evaporator coil surface, which increases the rate at

which water is condensed from the air passing through
the coil. Removing water from the air reduces the
relative humidity. When the relative humidity sensed is
2% below the set point (function code Cd33), the
Controller de-energizes the heat relay. The Controller

will continue to cycle heating to maintain relative
humidity below the selected set point.
Two timers are provided in the Dehumidification mode
to prevent rapid mode switching and consequent

contactor wear. They are:

S

Heater debounce timer (three minutes).

S

Out-of-range timer (five minutes).

The heater debounce timer is activated whenever the
heat contactor status is changed. The heat contactor
remains energized (or de-energized) for at least three
minutes even if the set point criteria are satisfied. This is

to prevent rapid cycling of the heat contactor when the
humidity set point is satisfied. If the mode is terminated
by a condition other than the humidity sensor, e.g., an