5-2

T-268-07

CONDITION

POSSIBLE CAUSE

REMEDY/

REFERENCE

SECTION

5.4 UNIT WILL NOT HEAT OR HAS INSUFFICIENT HEATING

No power to unit

Start-Stop switch OFF or defective

Circuit breaker OFF or defective

External power source OFF

Check

Check

Turn on

No control power

Circuit breaker or fuse defective

Transformer defective (TR)

Evaporator fan internal motor protector open

Heat relay defective

Heater termination switch open

Replace

Replace

6.15

Check

6.13

Unit will not heat or has insufficient

heat

Heater(s) defective

Heater contactor or coil defective

Evaporator fan motor(s) defective or rotating backwards

Evaporator fan motor contactor defective

Temperature controller malfunction

Defective wiring

Loose terminal connections

Low line voltage

6.14

Replace

6.15/6.16

Replace

5.9

Replace

Tighten

2.4

5.5 UNIT WILL NOT TERMINATE HEATING

Unit fails to stop heating

Temperature controller improperly set

Temperature controller malfunction

Heater termination switch remains closed along with the

heat relay

Reset

5.9

6.13

5.6 UNIT WILL NOT DEFROST PROPERLY

Will not initiate defrost automatically

Defrost timer malfunction

Loose terminal connections

Defective wiring

Defrost termination sensor defective or heat termination

switch open

Heater contactor or coil defective

3.1.4

Tighten

Replace

Replace

Replace

Will not initiate defrost manually

Manual defrost switch defective

Defrost termination sensor open

Replace

4.4.6

Initiates but relay (DR) drops out

Low line voltage

2.4

Initiates but does not defrost

Heater contactor or coil defective

Heater(s) burned out

Replace

6.14

Frequent defrost

Wet load

Normal