Compressor

Starting Sequence

Is Ambient

Temperature Less

Than 60 ˚F ?

High Speed Start

Has Set Point

Been Reached ?

STEP

A

B

C

D

E

YES

YES

YES

Low Speed

Soft Start

(See Note A & B)

Run For 2

Minutes

NO

NO

Continue In

High Speed

NOTE B

Low Speed Soft Start is

performed by closing the
SMV to 0% opening for ten
seconds during the start-up
of the compressor. The SMV
opening is then gradually

increased to the desired value
at the rate of a 3% opening
per second.

NO

Has Set Point

Been Reached ?

Compressor Cycles OFF

NOTE A

During

compressor

operation, if at anytime the
High Pressure Switch (HPS)
trips, the logic will switch to
Low Speed Soft Start.

Figure 3-7. Two-Speed Compressor Speed Change Logic -- Frozen Range Only