Industrial Data Systems IDS Scale Basic User Manual

Page 17

Advertising
background image

Scale Basic 4.2E

Tutorial

The Setpoint Monitor is used to generate the next event. When the setpoint event occurs, it
activates user function 2 which turns off the fill valve.

Event

Function

Comments

F1 key

User 1

Start Fill operation

Setpoint 1

User 2,

trigger when Net >= Fixed43 (setpoint amount)


Configure the Setpoint 1 event with the Upper register = Fixed43 and the Lower register = Net
weight register. This will cause the setpoint to trigger when the Net weight >= (greater than or
equal to) the value in Fixed 43. Configure the Setpoint 1 function to execute = User 2.

Register Fixed43 is chosen because the fill amount is fixed. Data in the Fixed registers is written
to EA-ROM which remains unchanged by power loss.

Function

Instructions

Comments

User 1

Copy, Tare, Gross

Tare the scale

Relay on, 1

Turn on fill valve

Set pt on, 1

Turn on setpoint monitor 1

End

End

of

function


User 2

Relay off, 1

Turn off fill valve

End

End

of

function


Parameter

Used

for

Fixed

43 setpoint

amount.


Use the template above to enter the program.

1.

Invoke the EZ Link program.

2.

Click on Reset to Defaults to clear previous program.

3.

Set Keyboard Events / F1 key = User1

4.

In Setpoint Events / Setpoint 1 set Upper = Fixed43, Lower = Net, Function = User2

5.

In Fixed Registers / Fixed43 enter 500.

6.

Scale Basic / User 1 enter the following program:
Function

Instructions

Comments

User 1

Copy, Tare, Gross

Tare the scale

Relay on, 1

Turn on fill valve

Set pt on, 1

Turn on setpoint monitor 1

End

End

of

function


5. Scale Basic / User 2 enter the following program:

Function

Instructions

Comments

User 2

Relay off, 1

Turn off fill valve

End

End

of

function