Maintenance

(Cont.)

Leak test check valves at least every three
months, as follows:

1. Shut off fuel cylinder valve and

disconnect hose from check valve.

2. Set oxygen regulator to 5 PSI and

open all gas valves on torch and
cutting attachment.

3. Plug torch tip and check for reverse

flow to fuel gas check valve. Use
soapy water or immerse in water to
check for leak. Set pressure to zero
after test.

4. Reconnect fuel gas hose and

disconnect oxygen hose.

5. Set fuel cylinder valve to 5 PSI and

inspect for leaks in oxygen check
valve.

Replace leaking
check valves or

have serviced by a qualified technician.

6. Reconnect hose and purge system

before use.

HOSES

Examine the hoses

carefully before

each use. If cuts, burns, worn areas or
damaged fittings are found, replace the
hose.

!

CAUTION

!

WARNING

ACETYLENE CYLINDERS

If horizontal
stowage is necessary,

or an acetylene cylinder is inadvertently
left lying in a horizontal position, it must
be placed in an upright position for a
minimum of two hours before it can be
used. Otherwise, acetone in which the
acetylene is dissolved will be drawn out
with the gas. By dissolving acetylene in
acetone, pressures above 15 PSIG are
safely attainable. If enough acetone is
removed, the cylinder may become
unstable and explode.

!

DANGER

Portable Oxy-Fuel Welding and Cutting Outfit