UNIT SIZE

48MPD,E

WEIGHT

A

B

C

D

E

F

lb

kg

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

82N

22,660

10 295

3646

11-11

9

16

6734

22- 1

1

8

1753

5-9

13 957

45-9

1

2

15 202

49-10

1

2

90P

24,660

11 203

1938

6- 4

5

16

2572

8-5

1

4

7283

23-10

3

4

1765

5-9

1

2

14 821

48-7

1

2

16 066

52- 8

1

2

10R

25,110

11 408

1938

6- 4

5

16

2572

8-5

1

4

7268

23-10

1

8

1759

5-9

1

4

14 821

48-7

1

2

16 066

52- 8

1

2

NOTES:
1. Dimensions in [

] are in millimeters.

2.

Center of gravity includes exhaust fan and high heat options. Unit weight
does not include exhaust fan or high heat options.

3. High heat add: 260 lb [118 kg]

Exhaust fan add: 2275 lb [1034 kg] on 82N

2400 lb [1090 kg] on 90P and 10R

4. Unit clearances:

Top — Do not restrict condenser fans, control box end — 6

Ј

-0

Љ

.

Sides — 6

Ј

-0

Љ

(except on return fan equipped units — 10

Ј

-0

Љ

).

Economizer end — 6

Ј

-0

Љ

(except power exhaust units — 10

Ј

-0

Љ

).

For smaller service and operational clearances, contact Carrier Application En-
gineering Department.

5. Downshot ducts designed to be attached to accessory roof curb. If unit is mounted

on dunnage, it is recommended the ducts be supported by cross braces as done
on the accessory roof curb.

Fig. 4 — Base Unit Dimensions, 48MP82N-10R