Fig. 46 — psychrometric chart for enthalpy control, Fig. 48 — keypad and display module (hsio) 36 – Carrier 50MP62L-10R User Manual

Page 36

Advertising
background image

KEYPAD AND DISPLAY MODULE (HSIO)
CONFIGURATION

IMPORTANT: The HSIO keypad and display module
is required for initial start-up of these units. All units
are shipped in standby mode, and the HSIO should be
used to change the unit to run mode. Once the unit is
in run mode, the HSIO is not required for normal
operation.

The keypad and display module provides unit function in-

formation at the unit. See Fig. 48. The module consists of a
keypad with 6 function keys, 5 operative keys, 10 numeric
keys (0 through 9), and an alphanumeric 8-character liquid
crystal display (LCD). Key usage is explained in Table 23.
Each function has one or more subfunctions.

The HSIO keypad and display module is installed by con-

necting the power and communication plugs and can be
easily moved from one unit to another. Because of this flex-
ibility, one HSIO can be used for several units.

Unit operation is controlled by the status of the run/

standby mode on the HSIO. To access the mode, press

on the HSIO keypad, and then press

.

The HSIO will display either STBY YES or STBY NO.

CLEAR

ENTER

To enable the unit, press

or

and press

while

at the STBY YES display. To disable the unit, press

ENTER

while at the STBY NO display. Clearing an alarm

that has stopped unit operation is accomplished by entering
the STBY YES mode.

IMPORTANT: Use the STBY YES mode when ser-
vicing the unit or running the quick test feature.

IMPORTANT: If remote start function is used, place
LOCAL/REMOTE switch in Local (OFF) position when
ever unit is placed in STBY YES.

SET UNIT TYPE — The correct unit type must be set. The
default unit type is VAV. If the unit is being used in a VAV
application, then the unit type does not need to be changed.

Table 23 — HSIO Keypad Key Usage

FUNCTION

KEYS

USE

Status — To display diagnostic codes and
current operating information about the unit.

Quick Test — To check inputs and outputs for
proper operation.

History — To check most recent alarms.

Service — To enter specific unit configuration
information.

Set Point — To enter operating set points and
day/time information.

Schedule — To enter occupied/unoccupied
schedules for unit operation.

OPERATIVE

KEYS

USE

Expand Display — To display a non-
abbreviated expansion of the display.

CLEAR

Clear — To clear the screen and return to previous
display. Also used to enter data value
of zero.

Up Arrow — To return to previous display position.

Down Arrow — To advance to next display position.

ENTER

To enter data.

CONTROL

CURVE

CONTROL POINT

(Approx Deg F)

AT 50% RH

A

73

B

68

C

63

D

58

Fig. 46 — Psychrometric Chart for

Enthalpy Control

NOTES:
1. Switches shown in high enthalpy state. Terminals 2 and 3 close on enthalpy

decrease.

2. When standard economizer is used with accessory differential enthalpy sen-

sor, set enthalpy control to ‘‘D’’ setting.

Fig. 47 — Wiring Connections for Solid-State

Enthalpy Sensor (HH57AC077)

1

2

3

4

5

6

7

8

9

0

-

STAT

SET

SCHD

EXPN

EDIT

SRVC

HIST

ALGO

TEST

ALRM

CLEAR

ENTER

Fig. 48 — Keypad and Display Module (HSIO)