CONTROL CONFIGURATION

KEYBOARD

ENTRY

DISPLAY

DESCRIPTION

VALUES IN [

] INDICATE FACTORY DEFAULTS

LOG ON

Enter password followed by

ENTER

LOGGEDON

Logged on okay

FACT CFG

Factory configuration

TYPE X

Unit type (0 = CV, 1 = VAV) [Default is 1]

ENTER

x

TYPE X

Verify unit type and change if necessary. If CV unit, see CV
control configuration.

DTRS

Data Reset
Enable Data Reset

ENTER

FACT CFG

Factory Configuration

LLAG X

Use

to access lead/lag option — disable with

HGBP (Item D, page CL-1)

ENTER

DISABLE

Disable lead/lag (0 = DIS, 1 = ENB) [1]

BLD PRES

Configure building pressure control (modulating power
exhaust)

BPS .05

Use

for building pressure set point (range 0 to .5) [.05]

ENTER

x

BPS X

Set building pressure set point per job requirements

LOGGEDON

Access log on/off function

LOG OFF

Use

to access log off

ENTER

LOGD OFF

Logged off okay

INPUTS

Run quick test to verify operation of unit functions
(see Controls and Troubleshooting Guide)

through

SETPOINT

Set system set points per job requirements

OHSP X

Set occupied heat set point (Range 55-80 F) [68] CV only

OCSP X

Set occupied cool set point (Range 55-80 F) [78] CV only

UHSP X

Set unoccupied heat set point (Range 40-80 F) [55]

UCSP X

Set unoccupied cool set point (Range 75-95 F) [90]

SPSP X

Set supply duct pressure set point (Range 0-5.0 in. wg) [1.5]

SASP X

Set supply air set point temperature (Range 45-70 F) [55]

TIME

Current time/date

dow.hh.mm

Set day of week and time

mm.dd.yy

Set month, day, and year

DAYLIGHT

Set daylight savings time begin/end dates. Required if job
conditions require adjustment of clock for daylight savings time
(see Controls and Troubleshooting Guide)

HOLIDAY

Set holiday dates. Required if job conditions require a different
schedule on holidays than other days (see Controls and Trouble-
shooting Guide)

PERIOD X

Set occupied/unoccupied schedules. Required if job condi-
tions require unit to enter unoccupied cycle at programmed
times of day or days of week (see Controls and Troubleshoot-
ing Guide)

through

NOTE: Data in brackets [

] is default value.

CL-3