START-UP CHECKLIST

MODEL NO.:

DATE:

SERIAL NO.:

TECHNICIAN:

I. PRE-START-UP:

Ⅺ VERIFY THAT UNIT IS LEVEL
Ⅺ VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT
Ⅺ LOOSEN ALL SHIPPING HOLDDOWN BOLTS AND REMOVE SHIPPING BRACKETS PER INSTRUCTIONS
Ⅺ VERIFY THAT COMPRESSOR SUSPENSION SPRINGS HAVE BEEN LOOSENED PER INSTRUCTIONS
Ⅺ VERIFY ASSEMBLY OF ECONOMIZER HOOD
Ⅺ VERIFY INSTALLATION OF EXHAUST HOOD
Ⅺ VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS
Ⅺ VERIFY THAT POWER SUPPLY MATCHES UNIT DATA PLATE
Ⅺ VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT
Ⅺ CHECK GAS PIPING FOR LEAKS (48MP ONLY)
Ⅺ CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE
Ⅺ CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREW

IS TIGHT

Ⅺ VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED
Ⅺ OPEN SUCTION, DISCHARGE, AND LIQUID LINE SERVICE VALVES
Ⅺ CHECK COMPRESSOR OIL LEVEL SIGHT GLASS AND VERIFY PROPER LEVEL
Ⅺ VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR 24 HOURS
Ⅺ CHECK VOLTAGE IMBALANCE

LINE-TO-LINE VOLTS:

AB

V

AC

V

BC

V

(AB + AC + BC)/3 = AVERAGE VOLTAGE =

V

MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =

V

VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =

%

IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!
CALL LOCAL POWER COMPANY FOR ASSISTANCE.

II. PRELIMINARY CHECKLIST ITEMS

(DETERMINE BEFORE CONFIGURING CONTROLS):

CONTROL SETTINGS FOR NON-NETWORKED, FREESTANDING UNIT

Ⅺ UNIT TO BE OPERATED ON CONSTANT AIR VOLUME (CV) RATHER THAN VARIABLE-AIR VOLUME (VAV)
Ⅺ CONFIRM THAT SPACE TEMPERATURE SENSOR (T55) HAS BEEN WIRED CORRECTLY PER SPACE

TEMPERATURE SENSOR (T55) SECTION ON PAGE 17.

Ⅺ CONFIRM THAT TUBING FOR SPACE AND SUPPLY DUCT PRESSURES HAS BEEN INSTALLED
Ⅺ SET ENTHALPY CONTROL SET POINT ON ECONOMIZER
Ⅺ SET SUPPLY FAN AND ‘‘CHECK FILTER’’ STATUS SWITCHES FOR JOB REQUIREMENTS

UNIT OPTION CHECKLIST

ITEM

PRESENT?

A

CONSTANT VOLUME POWER EXHAUST

B

VARIABLE VOLUME POWER EXHAUST

C

VARIABLE FREQUENCY DRIVE ON SUPPLY FAN (VAV ONLY)

D

HOT GAS BYPASS

E

VAV WITH OCCUPIED HEAT