If the unit is being used in a CV application, then perform
the following:
1. Enter the configuration function by pressing

and

.

2. Scroll down to unit type. TYPE 1 will be displayed.

ENTER

3. Press

and

to change the unit type to CV.

4. Scroll down to data reset. DTRS will be displayed. Press

ENTER

and

to save changes.

The fan operation type should also be configured for

use in occupied time periods. Fan operation can be

set to continuous or auto. To set, press

to enter

the subfunction. Scroll down to fan mode (FANM). Press

ENTER

ENTER

and

to set to AUTO. Press

and

to set

to continuous.
ENTER JOB SET POINT VALUES — The set point func-
tion allows the user to view the current values set for the
unit. From this function, the user can change the values.

Reading and Changing Set Points — To change the set point
of a particular feature, enter the appropriate subfunction and
scroll to the variable desired. Once the desired variable has

ENTER

been reached, type in the new value and press

. The

new value will appear in the display.

For example, the occupied cool set point is currently set

at the default value of 78 F. To change the occupied set point
to 72 F:

1. Press

to enter the occupied cool set point

function. The display will read OCSP 78.

2. Press

and the display will read OCSP 72.

ENTER

Set points can be changed by the user provided that the

values are within the allowable range for the input. If the
input is not within the allowable range, the original value
will remain displayed. See Table 24 for allowable ranges and
default values.

To change the demand limit set points, the functions must

first be enabled in the field configuration subfunction.

CONFIGURE UNIT CONTROLS AND FUNCTIONS —
Refer to Table 25 for a suggested sequence for entering
Basic System Configuration data. These values may be changed
from the HSIO at any time. If changing default values via
the CCN, the 48/50MP unit must first be in run mode
(STBY NO).

NOTE: After changing any of the values in the
configuration group, enable the Data Reset function.

QUICK TEST FUNCTION — Enable and run the Quick Test
function. Refer to the Controls and Troubleshooting manual
for more information on Quick Test.

Table 24 — Set Point Ranges and Defaults

DISPLAY

SET POINT

DESCRIPTION

DEFAULT

VALUE

ALLOWABLE

RANGE

BPSP

Building pressure set point

0.05 in. wg

0 to .50 in. wg

ECSO*

Economizer set point offset

3

1 to 10

HHL†/HHOR*

High humidity override (percent)

99%

0 to 100%

HTMP

High temperature minimum position

35 F

0 to 100 F

HUSP

Humidity set point (percent)**

40%

0 to 100%

IAQS†

IAQ set point

650 ppm

0 to 2000 ppm

LIMT†

Reset limit (F)

10 F

0 to 20 F

LSP

Loadshed set point (percent)

50%

0 to 100%

LTMP

Low temperature minimum position

10 F

0 to 100 F

MDP†

Minimum damper position (percent)

20%

0 to 100%

NTLO†

NTFC lockout temperature (F)

50 F

40 to 70 F

OLS†/OACS*

Outdoor-air cfm set point

1 cfm

0 to 50,000 cfm

OCSP

Occupied cool set point (F)**

78 F

55 to 80 F

OHSP

Occupied heat set point (F)**

68 F

55 to 80 F

PES†

Power exhaust on set point (percent)

90%

30 to 100%

RTIO†

Reset ratio (F)

3 F

0 to 10 F

SASP

Supply air set point (F)

55 F

45 to 70 F

SPSP

Static pressure set point††

1.5 in. wg

0 to 5.0 in. wg

UCDB*

Unoccupied cooling deadband

1

0 to 10

UCSP

Unoccupied cool set point (F)**

90 F

75 to 95 F

UHDB*

Unoccupied heating deadband

1

0 to 10

UHSP

Unoccupied heat set point (F)**

55 F

40 to 80 F

LEGEND

IAQ

Indoor-Air Quality

NFTC — Unoccupied Free Cooling
ppm

Parts Per Million

*These items are found under the Service function, and can only be accessed using either the Build-

ing Supervisor or Service Tool.

†These items are found under the Service function.

**Occupied space.

††Supply duct.

NOTE: Set points HHL/HHOR and OCS/OACS are displayed differently on the HSIO and Building Su-
pervisor. The set points are shown as HHL and OCS on the HSIO. The set points are shown as HHOR
and OACS on Building Supervisor or Service Tool.