Carrier comfort network interface, Fig. 29 — optional vfd — wiring connections 23 – Carrier 50MP62L-10R User Manual

Page 23

Advertising
background image

Carrier Comfort Network Interface

— The

48/50MP units can be connected to the CCN if desired. The
communication bus wiring is supplied and installed in
the field. It consists of shielded, 3-conductor cable with
drain wire.

The system elements are connected to the communication

bus in a daisy chain arrangement. The positive pin of each
system element communication connector must be wired to
the positive pins of the system element on either side of it,
the negative pins must be wired to the negative pins, and the
signal pins must be wired to signal ground pins. Wiring con-
nections for CCN should be made at the 4-pin plug (COMM)
located at the bottom right side of the fuse bracket in the
main control box. Consult CCN Contractor’s Manual for fur-
ther information.
NOTE: Conductors and drain wire must be 20 AWG mini-
mum stranded, tinned copper. Individual conductors must
be insulated with PVC, PVC/nylon, vinyl, Teflon, or poly-
ethylene. An aluminum/polyester 100% foil shield and an

outer jacket of PVC, PVC/nylon, chrome vinyl, or Teflon
with a minimum operating temperature range of

Ϫ20 C to

60 C is required. See Table 7 for cables that meet the
requirements.

Table 7 — CCN Connection Approved

Shielded Cables

MANUFACTURER

CABLE PART NO.

Alpha

2413 or 5463

American

A22503

Belden

8772

Columbia

02525

IMPORTANT: When connecting the CCN communi-
cation bus to a system element, use a color coding sys-
tem for the entire network to simplify installation and
checkout.

T3

T2

T1

GROUND

L1

L2

L3

(R)

(S)

(T)

FI

FC

S1

SC

3

1

IFR (SUPPLY
PER (EXHAUST)

VOLTAGE
SELECTOR

G

46

47

+

-

43

44

PECB (EXHAUST)
IFCB (SUPPLY)

PEC (EXHAUST)
IFC (SUPPLY)

L3

L2

L1

VFD

460V

SHIELD

(SUPPLY)
PSIO1
J6
CHANNEL 16

(EXHAUST)
PSIO1
J6
CHANNEL 15

+

-

EFM
(EXHAUST)
IDFM
(SUPPLY)

LEGEND

EFM

Exhaust Fan Motor

IDFM

Indoor Fan Motor

IFC

Indoor Fan Contactor

IFCB

Indoor Fan Circuit Breaker

IFR

Indoor Fan Relay

PEC

Power Exhaust Contactor

PECB — Power Exhaust Circuit Breaker
PER

Power Exhaust Relay

VFD

Variable Frequency Drive

Fig. 29 — Optional VFD — Wiring Connections

23

Advertising
This manual is related to the following products: