Table 5 — electrical data – Carrier 50MP62L-10R User Manual

Page 16

Advertising
background image

Table 5 — Electrical Data

UNIT

48MP/

50MP

VOLTAGE

3 Ph, 60 Hz

VOLTAGE

RANGE

COMP

NO. A1

COMP

NO. A2

COMP

NO. B1

COMP

NO. B2

CONDENSER

FAN

MOTORS

EVAPORATOR

FAN MOTOR

POWER

EXHAUST

FAN MOTOR

MCA

MOCP

Min

Max

RLA

LRA

RLA

LRA

RLA

LRA

RLA

LRA

Qty

FLA

Hp

FLA

Hp

FLA

Hp

62L

460

414

508

65.4

345

65.4

345

6

3.3

1

40

30

207.0

250

11

7.5

218.0

250

40

30

247.0

300

52

40

219.0

250

11

7.5

230.0

250

40

30

259.0

300

65

50

232.0

250

11

7.5

243.0

300

40

30

272.0

300

70M

460

414

508

46.8

253

34.6

173

65.4

345

6

3.3

1

52

40

235.0

300

11

7.5

246.0

300

52

40

287.0

350

65

50

248.0

300

11

7.5

259.0

300

52

40

300.0

350

77

60

262.9

300

11

7.5

273.9

350

52

40

314.9

350

82N

460

414

508

43.6

223

34.6

173

43.6

223

43.6

223

6

3.3

1

52

40

250.2

300

11

7.5

261.2

300

52

40

302.2

350

65

50

266.5

300

11

7.5

277.5

300

52

40

318.5

350

77

60

281.5

350

11

7.5

292.5

350

52

40

333.5

400

90P

460

414

508

43.6

223

46.8

253

43.6

223

46.8

253

8

3.3

1

65

50

288.5

350

14

10

302.5

350

65

50

353.5

350

77

60

303.5

350

14

10

317.5

350

65

50

368.5

400

96

75

327.5

400

14

10

341.5

400

65

50

392.2

450

10R

460

414

508

43.6

223

65.4

345

43.6

223

46.8

253

8

3.3

1

65

50

307.2

350

14

15

321.1

350

77

60

387.1

450

77

60

322.1

350

14

15

336.1

400

77

60

399.1

450

96

75

345.8

400

14

15

359.8

450

77

60

422.8

500

LEGEND

COMP — Compressor
FLA

Full Load Amps

Hp

Nominal Horsepower

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps (for wire sizing)

MOCP — Maximum Overcurrent Protection
RLA

Rated Load Amps

16

Advertising
This manual is related to the following products: