Appendix h – AERCO BMS II BOILER User Manual

Page 105

Advertising
background image

APPENDIX H

H-13

APPENDIX H

(cont.)

__________________________


Table H-2. BMS II Standard Holding Register Address Mapping

Modbus Data

Address (Hex)

Menu Item

Units and Range

Default/Comments

0x0083

Outside Temp
Sensor Offset

-50 to +50°F

Default = 0

0x0084

Dyn Up

0 to 300

Default = 20

0x0085

Dyn Down

0 to 300

Default = 200

0x0086

Fault Alarm Boilers

0 = No Blr Faults
1 = All Blr Faults

Default = 0

0x0087

4 to 20 mA Current
Offset

-1.00 mA to 1.00 mA

Default = 0

0x0088

Return Sensor
Offset

-10.0°F to 10.0°F

Default = 0

0x0089

Load Start Pct

1 to Blr Start Level

Default = 1

0x008A

Load Stop Pct

0 to Load Start -1

Default = 0

0x008B

Thru

0xFFFF

(Reserved For
Future Expansion)

Undefined