Outdoor reset mode, Operation – AERCO BMS II BOILER User Manual

Page 50

Advertising
background image

OPERATION

3-18

OUTDOOR RESET MODE

Perform the procedure described for the CONSTANT SETPT MODE and then continue with the steps
described below:

MENU & OPTION

ACTION

1. FIELDADJUST MENU



HEADER SET MODE

Set to OUTDOOR RESET

RESET RATIO

Enter a different value, if required (default = 1.2). Refer to
Appendix C.

BLDG REF TEMP

Enter the desired Building Reference Temperature.

Default = 70°F (Refer to Appendix C).

2. CONFIGURATION MENU

FAIL SAFE MODE

Set to CONSTANT SETPT if you want to maintain a Constant
Setpointt temperature in the event that the Outdoor Sensor signal
is lost. (Default = SHUTDOWN)

3. RELAY MENU

SYS START TEMP

Enter the outdoor temperature below which the system will be
activated.

4. CALIBRATION MENU

Required Only For Modulex Installations

LOAD START PCT

Enter a Value 2% Below the BLR START LEVEL

After completing the “Quick Start” procedure for any of the modes described above, check to ensure that
the “ON” LED is lit. If it is not, press the ON/OFF key to activate the BMS II.

For further programming details, refer to Chapter 4.