Appendix h – AERCO BMS II BOILER User Manual

Page 99

Advertising
background image

APPENDIX H

H-7

APPENDIX H

(cont.)

__________________________


Table H-2. BMS II Standard Holding Register Address Mapping

Modbus Data

Address (Hex)

Menu Item

Units and Range

Default/Comments

0x0012

Derivative Gain

-2.00 to 2.00
(0.00 increments)

Default = 0.15
(Value x 100)

0x0013

Header Temp
Bandwidth

5 to 120°F

Default = 70°F

0x0014

Aux Relay Open

0 to 99%

Default = 45%

0x0015

Aux Relay Mode

0 or 1
0 = 100% Fire Rate
1 = 100% Fire Rate and Off

Default = 1
(100% Fire Rate & Off)

0x0016

Failsafe Mode

0 or 1
0 = Shutdown
1 = Constant Setpt

Default = 0
(Shutdown)

0x0017

Fault Alarm Relay

Mode

0, 1, 2, 3
0 = All Faults,
1 = No Interlock
2 = Interlock 1
3 = Interlock 2

Default = 0
(All Faults)

0x0018

Fault Alarm Clear

Method

0 or 1
0 = Automatic
1 = Manual

Default = 0
(Automatic)

0x0019

Boiler Operation

Mode

0, 1 or 2
0 = Parallel
1 = Sequential
2 = Combination

Default = 1
(Sequential)

0x001A

Not Applicable

0x001B

(Reserved)

0x001C

(Reserved)

0x001D

(Reserved)

0x001E

Max Power Input

50 to 100%

Default = 100%
(Fire Rate)

0x001F

Sys Intlk Config

0 or 1
0 = Always Enabled
1 = Start Enabled

Default = 1
(Start Enabled)

0x0020

Real Time Clock
Minutes

00 to 59

Present Time