Appendix h – AERCO BMS II BOILER User Manual
Page 94

APPENDIX H
H-2
H
-1
BMS
II
S
TANDARD
I
NPUT
R
EGISTER
A
SSIGNMENMTS
The Read Only Input Register assignments for the BMS II are listed in Table H-1 which follows:
Table H-1. BMS II Standard Input Register Address Mapping
Modbus Data
Address (Hex)
Menu Item
Units and Range
Default/Comments
0x0000
(Reserved)
0x0001
Header Temperature
40 to 220°F
0x0002
Outside Air Temperature
-60 to 120°F
0x0003
Indoor Air/Return
Temperature
40 to 220°F
0x0004
Fire Rate Out
0 to 100%
(out to boilers)
0x0005
Header Set Temperature
40 to 220°F
0x0006
Network Address
128 to 247
Default = 128
0x0007
Total Boilers Fired
0 to 32 (for BMS II)
0x0008
Total Boilers On Line
0 to 32
0x0009
(Reserved)
0x000A
Fault/Message Code
0 to 65535
Bit:
0 = Outside Air Sensor
1 = Header Sensor Error
2 = Interlock 1 Error
3 = Interlock 2 Error
4 = Indoor Air Sensor Error/
Return Sensor Error
5 = 4-20mA Input Error
0x000B
thru
0x000F
(Reserved)
0x0010
Lead Boiler Number
1 to 32