Appendix a, Bms ii menus – AERCO BMS II BOILER User Manual

Page 68

Advertising
background image

APPENDIX A

A-2

APPENDIX A

_____________________________

BMS II MENUS

- Continued

AVAILABLE CHOICES OR LIMITS

MENU LEVEL & OPTION

MINIMUM

MAXIMUM

DEFAULT

RS485 MENU

RS485 BAUDRATE

2400, 4800,

9600, 19200

9600

MIN SLAVE ADDR

000

127

000

MIN SLAVE ADDR

000

127

000

NUMBER NETW BLRS

00

32

02

MODBUS CNTL TYPE

ROUND ROBIN,

BROADCAST

ROUND ROBIN

NETW BOILER 01
ADDRESS =

000

127

001

NETW BOILER 02
ADDRESS =

000

127

002

NETW BOILER 03
ADDRESS =

000

127

000

Etc., Up To:

NETW BOILER 32
ADDRESS =

000

127

000

FIELD ADJUST MENU

HEADER SET MODE

CONSTANT SETPOINT,

OUTDOOR RESET,

REMOTE SETPOINT

CONSTANT

SETPOINT

HDR HIGH LIMIT

040°F

220°F

200°F

HDR LOW LIMIT

040°F

220°F

040°F

INTERNAL SETPT

040°F

220°F

160°F

RESET RATIO
(Displayed Only if
HDR SET MODE =
OUTDOOR RESET)

0.3

3.0

1.2

BLDG REF TEMP

(Displayed Only If
HDR SET MODE =
OUTDOOR RESET)

40°F

220°F

70°F

REMOTE SIGNAL

(Displayed Only If HDR SET MODE
= REMOTE SETPT

4 – 20 mA,

MODBUS

4 - 20 mA