Appendix g, Table g-1. bms ii commands – (continued) – AERCO BMS II BOILER User Manual
Page 91

APPENDIX G
G-7
APPENDIX G
(cont.)
__________________________
Table G-1. BMS II COMMANDS – (Continued)
No.
COMMAND
ENTRY RANGE
FACTORY DEFAULT
129
Modbus Pass-Thru
0 = Disabled
1 = Enabled
0 = Disabled
130
Header Temp Deadband
01 to 15°F
05°F
131
Outside Temp Sensor Offset
-10.0°F to 10.0°F
0.0°F
132
Ramp Up %/Min
000 to 300
20
133
Ramp Down %/Min
000 to 300
200
134
Fault Alarm Boilers
No Blr Faults
All Blr faults
No Blr Faults
135
4-20 mA Offset
-1.00 to 1.00 mA
0.0 mA
136
Return Sensor Offset
-10.0 to 10.0°F
0.0°F
137
Load Start Pct
000 to 100
1
138 Load Stop Pct
000 to 100
0
150
I/O Status
00 to 255
Bit 0 = AUX Relay
Bit 1 = Fault Relay
Bit 2 = Sys Start Relay
Bit 3 = Empty
Bit 4 = Setback
Bit 5 = Interlock 2
Bit 6 = Interlock 1
Bit 7 = Empty
151
&
Up
(Reserved For Future Expansion)
Undefined