Remote setpt mode, Operation – AERCO BMS II BOILER User Manual
Page 49

OPERATION
3-17
REMOTE SETPT MODE
Perform the procedure described for the CONSTANT SETPT MODE and then continue with the steps
described below:
MENU & OPTION
ACTION
1. FIELD ADJUST MENU
HEADER SET MODE
Set to REMOTE SETPT
HDR HIGH LIMIT
Enter the maximum temperature for the Remote Setpoint input
(this will be the temperature equivalent to a 20 mA input) Default
= 200°F
HDR LOW LIMIT
Enter the minimum temperature for the Remote Setpoint input
(this will be the temperature equivalent to a 4 mA input) Default =
40°F
REMOTE SIGNAL
Select 4-20 mA (default) or MODBUS
2. CONFIGURATION MENU
FAIL SAFE MODE
Set to CONSTANT SETPT if you want to maintain a Constant
Setpoint temperature in the event that the Remote signal is lost.
(Default = SHUTDOWN)
3. CALIBRATION MENU
Required Only For Modulex Installations
LOAD START PCT
Enter a Value 2% Below the BLR START LEVEL