Appendix e, Bms ii wiring diagram – AERCO BMS II BOILER User Manual

Page 81

Advertising
background image

APPENDIX E

E-1

APPENDIX E

_____________________________

BMS II WIRING DIAGRAM

1

11

2

3

4

5

6

+

7

-8

9

10

12

13

14

OUT

AIR

SENS

HDR

SEN

4-20

MA

INT1

INT2

SET

BACK

485 ISO GND

485 B

+

485 A

-

RXD

TXD

ISO 12

V

FLT

ALARM

AUX

N

L

SYS

START

SHLD

RTN

85

265

VAC

TERMINALS

PROVIDE

12

VDC

@

15

mA

RELAYS RATED AT

120

VAC

,

5

A

&

FUSED

INTERNALLY AT

5

A

232 ISO GND

OUTSIDE AIR SENSOR

HEADER TEMP SENSOR

RETURN TEMP SENSOR

4 –

20

mA WHEN UTILIZED

CONTACT CLOSES ON

OUTSIDE AIR TEMP

CONTACT CLOSES ON

BMS FAULT CONDITION

CONTACT CLOSES WHEN

HEATING PLANT IS AT

MAX.

POWER INPUT

POWER INPUT

,

16

AWG

120

VAC

,

60

Hz

,

1

A

FUSED INTERNALLY

AT

1

A

SENSOR WIRING

(NOTE

1

)

INTERLOCKS

&

SETBACK WIRING

(NOTE

2

)

NOTES

:

1

.

AERCO RECOMMENDS USING TWO

-CONDUCTOR

,

TWISTED

,

SHIELDED PAIR

,

22

AWG CABLE

(BELDEN

9841

OR EQUIV

.)

-

TERMINATE SHIELDS AT BMS SHIELD

(SHLD

)

TERMINAL ONLY

.

-

DO NOT CONNECT SHIELDS AT SENSOR ENDS

.

-

DO NOT RUN SENSOR WIRING WITH POWER WIRING

.

2

.

CONTACTS PROVIDED BY OTHERS

.

USE CONTACTS RATED FOR

LOW SIGNAL LEVELS

.

JUMPER INTERLOCKS

(INT

1

,

INT

2

)

IF EXTERNAL CONTACTS ARE NOT USED

.

3

.

IF THE EMS BEING USED CONTAINS ONLY A RS

485

PORT

,

A RS

485

-TO

-RS

232

CONVERTER IS REQUIRED

.

IF NECESSARY

,

A

12

VDC OUTPUT IS PROVIDED

BY THE BMS II TO POWER THE RS

485

-TO

-RS

232

CONVERTER

,

RS

485

TO

BOILERS

RS

232

FROM EMS

(NOTE

3

)

TO SHLD

(TERM

. 3

)

IF NEEDED (NOTE

3)