8 review of all parameters, Am series cascade sequencer – AERCO AM Series Boiler Cascade Sequencer Controller User Manual
Page 19

AM Series Cascade Sequencer
INSTALLATION AND OPERATION MANUAL
1.8 Review of All Parameters
Figure 1-18 diagrams a cascade setup using three (3) AM1000 units (with four burner boards in
each unit).
At the end of the installation process, all parameters (Address; Switch S4; 2003; 3001 and
3050) should have the values as shown on Figure 1-18.
If an attempt is made to operate the cascade system and the applicable parameters are not set
to the values shown in Figure 1-18, one or more of the heaters in the cascade will display a 116
error (communication error) and will stop functioning.
Figure 1-18: Cascade General Configuration and Settings Diagram
OMM-0101_0A