4 sub-menu parameter descriptions, 5 menu parameter descriptions, Am series cascade sequencer – AERCO AM Series Boiler Cascade Sequencer Controller User Manual
Page 22
AM Series Cascade Sequencer
INSTALLATION AND OPERATION MANUAL
Submenu Navigation and Parameter Settings – Continued
4. Use the Up or Down buttons to change the parameter value up or down.
5. When the desired value is displayed, save it by pressing the Ok button. To reject the
change, do not press OK, and instead skip to the next step.
6. To leave the Sub Menu and return to the Main menu, press the Menu button (Figure 2-1).
IMPORTANT NOTE!
After any change to a parameter, wait at least 40 seconds before
exiting the sub menu or turning the power off.
2.4 Sub-Menu Parameter Descriptions
Below is a list of Menu parameters and descriptions. The table in the next section lists the range
and default settings for each parameter.
AM Series Cascade Sequencer Parameter Descriptions
Parameter Name
Parameter Description
Boiler address
Logic boiler address
Cascade setpoint
Cascade general sensor setpoint
DHW ON..OFF
Enable / disable control for an indirect water heater
Start delay time
Delay for a call of the next boiler
Stop delay time
Delay to remove the call to the next boiler
Start boiler diff
Temperature differential to call the next boiler
Stop boiler diff
Temperature differential to remove the call to the next boiler
Stop all boiler diff
Temperature differential to remove the call to all boilers
Max offset up
Maximum difference above the header setpoint that any one boiler is allowed to
reach.
Max offset down
Maximum difference below the header setpoint that any one boiler is allowed to
reach.
Rotation interval
How often the “lead” boiler is rotated.
P Value
Proportional band of the PID temperature control of the cascade general sensor
I Value
Integral band of the PID temperature control of the cascade general sensor
D Value
Derivative band of the PID temperature control of the cascade general sensor
Slew rate
Slew rate is a low level parameter. It determines how fast the output of a PID can
change per amount of time.
System correction
The system correction value is added to the measured system temperature. This
corrected value is used for control. If the measured sensor value deviates from the
real temperature then you can correct it with this parameter.
Mod delay factor
Delay to the start of modulation of any boiler.