AM Series Cascade Sequencer

INSTALLATION AND OPERATION MANUAL

Submenu Navigation and Parameter Settings – Continued

4. Use the Up or Down buttons to change the parameter value up or down.
5. When the desired value is displayed, save it by pressing the Ok button. To reject the

change, do not press OK, and instead skip to the next step.

6. To leave the Sub Menu and return to the Main menu, press the Menu button (Figure 2-1).

IMPORTANT NOTE!

After any change to a parameter, wait at least 40 seconds before

exiting the sub menu or turning the power off.

2.4 Sub-Menu Parameter Descriptions

Below is a list of Menu parameters and descriptions. The table in the next section lists the range

and default settings for each parameter.

AM Series Cascade Sequencer Parameter Descriptions

Parameter Name

Parameter Description

Boiler address

Logic boiler address

Cascade setpoint

Cascade general sensor setpoint

DHW ON..OFF

Enable / disable control for an indirect water heater

Start delay time

Delay for a call of the next boiler

Stop delay time

Delay to remove the call to the next boiler

Start boiler diff

Temperature differential to call the next boiler

Stop boiler diff

Temperature differential to remove the call to the next boiler

Stop all boiler diff

Temperature differential to remove the call to all boilers

Max offset up

Maximum difference above the header setpoint that any one boiler is allowed to

reach.

Max offset down

Maximum difference below the header setpoint that any one boiler is allowed to

reach.

Rotation interval

How often the “lead” boiler is rotated.

P Value

Proportional band of the PID temperature control of the cascade general sensor

I Value

Integral band of the PID temperature control of the cascade general sensor

D Value

Derivative band of the PID temperature control of the cascade general sensor

Slew rate

Slew rate is a low level parameter. It determines how fast the output of a PID can

change per amount of time.

System correction

The system correction value is added to the measured system temperature. This

corrected value is used for control. If the measured sensor value deviates from the

real temperature then you can correct it with this parameter.

Mod delay factor

Delay to the start of modulation of any boiler.

Page 22 of 26