CHAPTER 4: INITIAL START-UP

PR2: 05/09/12 Page

51 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

45. Press the ▼ arrow key until CAL Voltage 30% is displayed.
46. Press the CHANGE key. CAL Voltage 30% will begin to flash.
47. The oxygen level at the 30% valve position should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values

shown.

Table 4-5: Combustion Oxygen Levels for a 30% Air/Fuel Valve Position

Oxygen

%

± 0.2

Carbon

Monoxide

NOx

7.0 %

<50 ppm

<30 ppm

48. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow

key decreases the oxygen level.

49. Once the oxygen level is within the specified range at 30%, press the ENTER key to

store the selected blower output voltage for the 30% valve position.

50. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
51. Press the CHANGE key. SET Valve Position will begin to flash.
52. Press the ▼ arrow key until the SET Valve Position reads 16%, then press the ENTER

key.

53. Press the ▼ arrow key until CAL Voltage 16% is displayed.
54. Press the CHANGE key. CAL Voltage 16% will begin to flash.
55. The oxygen level at the 16% valve position should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values

shown.

Table 4-1: Combustion Oxygen Levels for a 16% Air/Fuel Valve Position

Oxygen

%

± 0.2

Carbon

Monoxide

NOx

8.0 %

<50 ppm

<30 ppm

56. If the oxygen level is not within the specified range, adjust the level using the ▲

and ▼

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow

key decreases the oxygen level.

57. Once the oxygen level is within the specified range at 16%, press the ENTER key to

store the selected blower output voltage for the 16% valve position.

58. This completes the natural gas combustion calibration procedure.

4.5 UNIT REASSEMBLY

Once the combustion calibration adjustments are properly set, the unit can be reassembled for

service operation.

1. Set the ON/OFF switch in the OFF position.