2 operation time log, 3 sensor log – AERCO BMK 1.5 LN July 2011 User Manual

Page 99

Advertising
background image

CHAPTER 9: RS232 COMMUNICATION

PR2: 05/09/12 Page

99 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

Operation Time Log

9.4.2

The Operation Time Log consists of a string of ASCII records stored in non-volatile memory within

the C-More Control Panel. Events such as power-up, ignition and turn-off are time stamped. Data

logged while the unit is running are run-length encoded. Data is logged or the run-length

incremented every 30 seconds. For a new run record to be logged, the fire rate or flame strength

must change by more than 5%, or the run mode must change. At steady-state, the run-length is

allowed to reach a maximum of 30 minutes before the record is logged. This means that no more

than 30 minutes of data can be lost if the unit loses power. Table 9-2 shows a sample Operation

Time Log for a boiler:
The Operation Time Log can only be accessed through the RS232 interface using a laptop or other

terminal device. Ten operation time records are displayed for each T command entry. The operation

time log can be cleared ONLY by factory authorized personnel using the Clear Log option in the

Factory menu.

NOTE:

The Sensor (S) Log can store up to 1200 records. Therefore,

to view the most recently logged record, enter “S” followed by

0 (zero) and then press Enter (i.e. S0 <Enter>). To view

earlier records in reverse chronological order, enter S and

press Enter. To go back 200 or 700 records, enter S200 or

S700, etc. and press Enter.

Sensor Log

9.4.3

The sensor values can be logged at a different rate if needed by setting the Sensor Log Interval in

the Diagnostics Menu. The log interval can vary from once every minute to once every day. Table 9-

3 shows a sample Sensor Log every 5 minutes for a boiler running in Constant Setpoint mode.

Table 9-1. Sample Fault Log Display

No.

Fault Message

Cycle

Date

Time

0 Direct Drive Signal Fault

609 1/10/02 8:42am

1 Low Gas Pressure

366 7/04/01 5:29pm

2 Loss of Power

0 1/01/01 11:50am

Table 9-2. Sample Operation Time Log Display

Status

Fire Rate Flame Run Length

Date

Time

Off, Direct Drive

0

0

8

1/15/02

2:35pm

Run, Direct Drive

38

100

34

1/15/02

2:27pm

Run, Direct Drive

31

100

30

1/15/02

1:53am

Run, Direct Drive

35

100

2

1/15/02

1:23pm

Run, Direct Drive

29

100

0

1/15/02

1:21pm

Ignition

0

0

0

1/15/02

1:20pm

Off, Switch

0

0

35

1/15/02

12:30pm

Run, Manual

40

100

0

1/15/02

11:55am

Ignition

0

0

0

1/15/02

11:55am

Power-up

0

0

0

1/15/02

11:50am

Advertising