CHAPTER 6: SAFETY DEVICE TESTING
Page
64 of 152 PR2: 05/09/12
Benchmark 1.5LN Low NOx Boiler
Operation and Maintenance Manual
OMM-0041_0D
GF-120
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
5. The unit should start once the adjustable temperature limit switch setting is above the actual
outlet water temperature.
FRONT VIEW
ADJUSTABLE
TEMPERATURE
LIMIT SWITCH
RESET BUTTON
FOR MANUAL
TEMPERATURE
LIMIT SWITCH
SEE
DETAIL “A”
DETAIL “A”
Figure 6-2: Temperature Limit Switch Setting
6. Once the adjustable over-temperature switch setting is approximately at, or just below, the
actual outlet water temperature, the unit should shut down. The
FAULT indicator should
start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should be
displayed. It should not be possible to restart the unit.
7. Reset the adjustable over-temperature switch to its original setting.
8. The unit should start once the adjustable temperature limit switch setting is above the actual
outlet water temperature.