Benchmark 1.5ln low nox boiler, Gf-120 – AERCO BMK 1.5 LN July 2011 User Manual

Page 91

Advertising
background image

CHAPTER 7: MAINTENANCE

PR2: 05/09/12 Page

91 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

PRG SWTCH

CLOSED

DURING IGNITION

(continued)

2. Defective or shorted switch.

3. Switch wired incorrectly.
4. Defective Power Supply Board or fuse
5. Defective IGST Board

2. If the Air/Fuel Valve does rotate to the ignition position, check

the purge switch for continuity between the N.O. and COM

terminals. If the switch shows continuity when not in contact

with the cam, check to ensure that the switch is wired correctly

(correct wire numbers on the normally open terminals).

3. If the switch is wired correctly, replace the switch.
4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.

PRG SWTCH OPEN

DURING PURGE

1. Defective purge switch.

2. No voltage present at switch.

3. Switch wired incorrectly.

4. Defective Power Supply Board or fuse
5. Defective IGST Board

1. If the air-fuel valve does rotate, check the purge switch for

continuity when closing. Replace switch if continuity does not

exist.

2. Measure for 24 VAC from each side of the switch to ground. If

24VAC is not present, refer fault to qualified service personnel.

3. Check to ensure that the switch is wired correctly (correct wire

numbers on the normally open terminals).

4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.

OUTDOOR TEMP

SENSOR FAULT

1. Loose or broken wiring.
2. Defective Sensor.

3. Incorrect Sensor.

1. Inspect Outdoor Temperature sensor for loose or broken wiring.
2. Check resistance of sensor to determine if it is within

specification.

3. Ensure that the correct sensor is installed.

REMOTE SETPT

SIGNAL FAULT

1. Remote setpoint signal not present:

Not yet installed.

Wrong polarity.

Signal defective at source.

Broken or loose wiring.

2. Signal is not isolated (floating) if 4 to 20 mA.
3. Control Box signal type selection switches

not set for correct signal type (voltage or

current).

1. Check I/O Box to ensure signal is hooked up.

Hook up if not installed.

If installed, check polarity.

Measure signal level.

Check continuity of wiring between source and boiler.

2. Check signal at source to ensure it is isolated.
3. Check DIP switch on PMC board to ensure it is set correctly for

the type of signal being sent. Check control signal type set in

Configuration Menu.

Advertising