CHAPTER 6: SAFETY DEVICE TESTING

Page

66 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

8. Once flame is proven, close the manual gas valve located between the SSOV (Figure 6-3)

and the Air/Fuel Valve.

9. The unit should shut down and execute an IGNITION RETRY cycle by performing the

following steps:
(a)

The unit will execute a shutdown purge cycle for a period of 15 seconds and display WAIT

FAULT PURGE.

(b)

The unit will execute a 30 second re-ignition delay and display WAIT RETRY PAUSE.

(c)

The unit will then execute a standard ignition sequence and display WAIT IGNITION RETRY.

10. Since the manual gas shutoff valve is still closed, the unit will fail the ignition retry sequence.

Therefore, it will shut down and display FLAME LOSS DURING IGNITION following the failed

ignition retry cycle.

11. Open the valve previously closed in step 8.
12. Press the CLEAR

button. The unit should restart and fire.

PARTIAL LEFT SIDE VIEW

BLOWER

PROOF

SWITCH

BLOCKED

INLET

SWITCH

AIR

INLET

AIR/FUEL

VALVE

SSOV

MANUAL

GAS

SHUTOFF

VALVE

Figure 6-3: Manual Gas Shut-Off Valve Location