Benchmark 2.0ln low nox boiler, Gf-123 – AERCO BMK 2.0 LN October 2012 User Manual

Page 102

Advertising
background image

Chapter 8

Benchmark 2.0LN Low NOx Boiler

GF-123

Troubleshooting Installation, Operation and Maintenance Manual

OMM-0046_0F

Page 102 of 172 AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

PR1 10/17/12

TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

FLAME LOSS

DURING IGN

(continued)

1. Unstable gas pressure.

2.

Carbon or other debris on Burner.

3.

Staged ignition solenoid valves don’t open.

4.

Clogged staged ignition piece.

1. Refer to “Gas Pressure Requirements” section of GF-2030:

BMK Gas Supply Design Guide.

2.

Remove the burner and inspect for any carbon or debris.
Clean and reinstall.

3.

When boiler goes to ignition, listen to the solenoid valves
for a clicking sound to ensure they are opening.

4.

Remove and inspect staged ignition piece for blockage.

FLAME LOSS

DURING RUN

1. Worn Flame Detector or cracked ceramic.

2. Defective Regulator.


3. Poor combustion calibration.

4. Debris on burner.

5. Blocked condensate drain.

1. Remove and inspect the Flame Detector for signs of wear or

cracked ceramic. Replace if necessary.

2. Check gas pressure readings using a gauge or manometer

into and out of the Air/Fuel Valve to ensure that the gas
pressure into and out of the valve is correct.

3. Check combustion calibration. Adjust as necessary.

4. Remove the burner and inspect for any carbon or debris.

Clean and reinstall.

5. Remove blockage in condensate drain.

HEAT DEMAND

FAILURE

1. The Heat Demand Relays on the Ignition/

Stepper board failed to activate when
commanded.

2. Relay is activated when not in Demand

1. Press CLEAR button and restart the unit. If the fault

persists, replace Ignition/Stepper (IGST) Board.

2. Defective relay. Replace IGST Board.

HIGH GAS

PRESSURE

1. Incorrect supply gas pressure.

2. Defective gas pressure adjustment in SSOV

Actuator.



3. Defective High Gas Pressure Switch



4. Gas pressure snubber not installed.

1. Check to ensure gas pressure at inlet of SSOV is 14” w.c.

maximum.

2. If gas supply pressure downstream of SSOV Actuator cannot

be lowered, to 2.8” W.C. (or 2.3” W.C. for propane), using
the gas pressure adjustment screw (see para. 4.3, step 10),
the SSOV Actuator gas pressure adjustment mechanism
may be defective. See para. 4.3, Step 10 (nat. gas) or 4.4,
Step 10 (propane).

3. Remove the leads from the high gas pressure switch and

measure continuity across the common and normally closed
terminals with the unit not firing. Replace the switch if it does
not show continuity.

4. See Figure 8-1. Ensure that the gas pressure snubber is

installed at the high gas pressure switch.

Advertising