Gf-123, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN October 2012 User Manual

Page 135

Advertising
background image

GF-123

Benchmark 2.0LN Low NOx Boiler

Appendix E

OMM-0046_0F

I

nstallation, Operation and Maintenance Manual Boiler Defaults

PR1 10/17/12

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288

Page 135 of 172

Table E-1: Boiler Default Settings (Continued)

MENU & OPTION

FACTORY DEFAULT

Configuration Menu - Continued

Pump Delay Timer

0 min

Aux Start On Dly

0 sec

Failsafe Mode

Shutdown

Analog Output

Valve Position 0-10V

CAUTION: DO NOT
Change

Low Fire Timer

2 sec

Setpt Limiting

Disabled

Setpt Limit Band (If Setpt Limiting = Enabled)

5°F

Network Timeout

30 seconds

Hi DB Setpt En

30

Demand Offset

10

Deadband High

2

Deadband Low

2

Spark Monitor

Disabled

Spark Current

0

Tuning Menu

Prop Band

70°F

Integral Gain

1.00

Derivative Time

0.00 min

Warmup Prop Band

95

Warmup Int Gain

50

Warmup PID Timer

20

Reset Defaults

No