Appendix e: boiler default settings, Benchmark 2.0ln low nox boiler, Gf-123 – AERCO BMK 2.0 LN October 2012 User Manual
Page 134
Appendix E
Benchmark 2.0LN Low NOx Boiler
GF-123
Default Settings Installation, Operation and Maintenance Manual
OMM-0046_0E
Page 134 of 172
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12
APPENDIX E: BOILER DEFAULT SETTINGS
Table E-1: Boiler Default Settings
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
BMK Boiler LN
Unit Size
2000 MBH (2.0 MBTU)
Fuel Type
Natural Gas
Boiler Mode
Constant Setpoint
Remote Signal
(If Mode = Remote Setpoint, Direct Drive or
Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit
60°F
Setpt Hi Limit
195°F
Temp Hi Limit
195°F
Max Valve Position
100%