Appendix F

Benchmark 2.0LN Low NOx Boiler

GF-123

Parts Lists Installation, Operation and Maintenance Manual

OMM-0046_0F

Page 138 of 172

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12

BENCHMARK 2 MIL. BTU LOW NOx

AP-A-798

GAS FIRED BOILER

DIMENSIONAL DRAWING

1) ALL DIMENSIONS SHOWN ARE IN INCHES (CENTIMETERS)

NOTES:

ASME B & PV CODE SECTION IV STAMP H

240

210

(PSIG)

TEST PRESS.

TEMP. (°F)

MAXIMUM

MAX. WORKING PRESS. (PSIG)

160

HEAT EXCHANGER & COMBUSTION CHAMBER DESIGN STANDARDS

HT'G SURFACE SQ.FT.

87

MIN. RELIEF VA. CAPACITY MBH

2000

2) RELIEF VALVE AND CONDENSATE TRAP ARE INCLUDED SEPARATELY IN SHIPMENT

JK

092608

INTERNATIONAL, INC.

AERCO

NORTHVALE, NJ 07647

APPD.

REV.DATE

SCALE

DWN.BY

CHKD.

DATE SIZE

REV

D

CONTROL PANEL DISPLAY

3/4" ELECTRICAL

CONDUIT CONNECTION

5

36

23

12-1/4

28

OPTIONAL CONNECTION FOR 8" DIAMETER SEALED COMBUSTION AIR DUCTWORK

LIFTING LUGS

79

56

71

7.00

13-1/4

15

7-3/4

12-3/4

23-1/2

2-1/2

1-1/4

7-1/2

18.00

THIS AREA TO BE ACCESSIBLE FOR MAINTENANCE

4"-150# FLG'D

HOT WATER OUTLET CONN.

2" NPT GAS INLET CONN.

4"-150# FLG'D COLD WATER INLET CONN.

1-1/2" NPT

DRAIN CONN.

8" EXHAUST

OUTLET

PRESS./TEMP.

GAUGE

PRESS. RELIEF VA.

CONDENSATE DRAIN

DOOR SWING

4" CONCRETE PAD -SET UNIT FLUSH AT REAR

(180.3)

(142.2)

(33.7)

(17.8)

(19.7)

(32.4)

(59.7)

(38.1)

(6.4)

(3.2)

(19.1)

(200.7)

(45.8)

(91.4)

(58.4)

(12.7)

(71.1)

(31.1)

(41.9)

3/4" NPT GAS VENT CONN. FOR "IRI GAS TRAIN OPTION" ONLY

16-1/2

“A”

74

BMK2.0 LN

MODEL

DIM. "A"

NAT. GAS WITH FM GAS TRAIN

18-3/4 (47.6)

17-1/2 (44.5)

(188.0)

NAT. GAS WITH IRI GAS TRAIN

Advertising