5 supply and return piping, 6 condensate drain and piping, Benchmark 2.0ln low nox boiler – AERCO BMK 2.0 LN October 2012 User Manual

Page 18: Gf-123

Advertising
background image

Chapter 2

Benchmark 2.0LN Low NOx Boiler

GF-123

Installation

Installation, Operation and Maintenance Manual

OMM-0046_0F

Page 18 of 172

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12

In multiple unit installations, it is important to plan the position of each unit in advance. Sufficient
space for piping connections and future service/maintenance requirements must also be taken
into consideration. All piping must include ample provisions for expansion.

If installing a Combination Control Panel (CCP) system, it is important to identify the
Combination Mode Boilers in advance and place them in the proper physical location. Refer to
Chapter 5 for information on Combination Mode Boilers.

2.5 SUPPLY AND RETURN PIPING

The Benchmark 2.0LN Boiler utilizes 4” 150# flanges for the water system supply and return
piping connections. The physical location of the supply and return piping connections are on the
rear of the unit as shown in Figure 2-3. Refer to Appendix F, Drawing AP-A-798 for additional
dimensional data.

2" GAS INLET
CONNECTION

BOILER RETURN
4" – 150# FLANGE
CONNECTION

BOILER SUPPLY

4" – 150# FLANGE

CONNECTION

EXHAUST

MANIFOLD

SHELL
DRAIN
VALVE

REAR VIEW

Figure 2-3: Supply and Return Locations

2.6 CONDENSATE DRAIN AND PIPING

The Benchmark 2.0LN Boiler is designed to condense water vapor from the flue products.
Therefore, the installation must have provisions for suitable condensate drainage or collection.

The condensate drain pipe located on the exhaust manifold (Figure 2-4) must be connected to a
condensate trap which is packed separately within the unit’s shipping container.

Advertising