Appendix E
Benchmark 2.0LN Low NOx Boiler
GF-123
Default Settings Installation, Operation and Maintenance Manual
OMM-0046_0E
Page 136 of 172
AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12
Table E-1: Boiler Default Settings (Continued)
MENU & OPTION
FACTORY DEFAULT
Combustion Cal – Natural Gas
CAL Voltage 18%
1.00v
CAL Voltage 30%
2.30v
CAL Voltage 45%
2.95v
CAL Voltage 60%
3.60v
CAL Voltage 80%
5.30v
CAL Voltage 100%
9.10v
SET Valve Position
0%
Blower Output
.00v
Combustion Cal - Propane
CAL Voltage 20%
1.10v
CAL Voltage 30%
1.95v
CAL Voltage 45%
3.00v
CAL Voltage 60%
3.00v
CAL Voltage 80%
4.45v
CAL Voltage 100%
8.20v
SET Valve Position
0%
Blower Output
.00v