Benchmark 2.0ln low nox boiler, Gf-123 – AERCO BMK 2.0 LN October 2012 User Manual

Page 136

Advertising
background image

Appendix E

Benchmark 2.0LN Low NOx Boiler

GF-123

Default Settings Installation, Operation and Maintenance Manual

OMM-0046_0E

Page 136 of 172

AERCO International Inc.● 100 Oritani Dr. ● Blauvelt, NY 10913. ● Ph: 800-526-0288 PR1 10/17/12

Table E-1: Boiler Default Settings (Continued)

MENU & OPTION

FACTORY DEFAULT

Combustion Cal – Natural Gas

CAL Voltage 18%

1.00v

CAL Voltage 30%

2.30v

CAL Voltage 45%

2.95v

CAL Voltage 60%

3.60v

CAL Voltage 80%

5.30v

CAL Voltage 100%

9.10v

SET Valve Position

0%

Blower Output

.00v

Combustion Cal - Propane

CAL Voltage 20%

1.10v

CAL Voltage 30%

1.95v

CAL Voltage 45%

3.00v

CAL Voltage 60%

3.00v

CAL Voltage 80%

4.45v

CAL Voltage 100%

8.20v

SET Valve Position

0%

Blower Output

.00v