32

P

IPE

S

IZING

- P

ROPANE

G

AS

Contact the local propane gas supplier for rec-
ommended sizing of piping, tanks and 100%
lockup gas regulator.

P

ROPANE

G

AS

S

UPPLY

P

RESSURE

R

EQUIREMENTS

• Adjust the propane supply regulator pro-

vided by the gas supplier for 13”w.c. maxi-
mum pressure

• Pressure required at the gas valve inlet

supply pressure port:

• Maximum 13”w.c. at fl ow or no fl ow condi-

tions to the burner

• Minimum 5”w.c. during fl ow conditions to

the burner. Must be verifi ed during start up
and with all other gas appliances operating
within the building.

GF-125