Filling the Boiler System

Check with local codes requirements for the
installation of backflow preventers or actual
disconnection from the boiler’s cold water fill
or make up water supply line.

N

OTICE

Massachusetts Code requires the in-
stallation of a backfl ow preventer if anti-
freeze is used.

Ensure the concentration of antifreeze to
water does not exceed a 50/50 ratio.

N

OTICE

System water, including additives, must
be practically nontoxic, having a toxicity
rating or Class of 1, as listed in Clinical
Toxicology of Commercial Products.

Filling the Boiler System

1. Close the boiler drain valve located on

the bottom of the unit and any manual or
automatic air vent in the system.

2. Open all system isolation valves.
3. Fill the boiler system to correct system

pressure. Correct pressure will vary with
each application.

N

OTICE

Typical residential system fi ll pressure
is 12 psi. System pressure will increase
when system temperature increas-
es. Operating pressure of the system
should never exceed 25 psi.

4. Purge air and sediment in each zone of

the boiler system through the purge valve.
Open air vents to allow air to be purged in
the zones.

5. Once the system is completely filled and

purged of all air and sediment, check the
system pressure and check/repair any
leaks.

WARNING!

U

NREPAIRED

SYSTEM

LEAKS

WILL

CAUSE

CON

-

TINUAL

MAKEUP

WATER

TO

BE

ADDED

TO

THE

BOILER

. C

ONTINUAL

MAKEUP

WATER

COULD

CAUSE

MINERAL

BUILDUP

WITHIN

THE

HEAT

EXCHANGER

,

REDUCING

THE

HEAT

TRANSFER

,

CAUSING

POSSIBLE

HEAT

BUILDUP

AND

EVEN

-

TUAL

HEAT

EXCHANGER

FAILURE

.

Check Low Water Cut-Off Device

• The Esteem 399 Low NOx is provided

with a factory installed LWCO device that
measures system pressure of more than
10 psi.

• Remove the front jacket panel and check

for continuity across the low water cut-off
device wire terminals. The contacts should
be closed when system pressure is greater
than 10 psi. See Figure 29 page 86 for loca-
tion of the LWCO.

Check For Gas Leaks

WARNING!

P

RIOR

TO

START

-

UP

AND

DURING

INITIAL

OP

-

ERATION

,

SMELL

CLOSE

TO

THE

FLOOR

AND

AROUND

THE

UNIT

FOR

GAS

ODORANT

OR

ANY

UNUSUAL

ODOR

. D

O

NOT

PROCEED

WITH

THE

START

-

UP

IF

THERE

IS

ANY

INDICATION

OF

A

GAS

LEAK

. A

NY

LEAKS

FOUND

MUST

BE

REPAIRED

IMMEDIATELY

.

WARNING!

P

ROPANE

INSTALLATIONS

ONLY

- T

HE

PROPANE

SUPPLIER

MIXES

AN

ODORANT

WITH

THE

PRO

-

PANE

TO

MAKE

ITS

PRESENCE

DETECTABLE

. I

N

SOME

CASES

THE

ODORANT

CAN

FADE

AND

THE

GAS

MAY

NO

LONGER

HAVE

AN

ODOR

.

P

RIOR

TO

START

-

UP

OF

THE

UNIT

AND

PERI

-

ODICALLY

AFTER

START

-

UP

HAVE

THE

PROPANE

SUPPLIER

CHECK

AND

VERIFY

THE

ODORANT

LEVEL

.

GF-125

Advertising