E 02, E 03, E 04 – AERCO Esteem O&M Manual User Manual

Page 85: E 05, E 06, E 07, E 08

Advertising
background image

79

GF-125

E 02

Continued

Failed Ignition Error

Boiler has failed to

establish flame detec-

tion during the igni-

tion sequence.

•

Flame is established during the ignition sequence, but not maintained. May be due to low

flame signal detection by Control module.

•

Inspect flame pattern on the burner head during high and low fire inputs (See page 49).

Inspect and clean the burner head. Replace the burner head if damaged.

•

Check the input rate of the boiler at the gas meter during high fire input. If the gas meter

measured rate is not at or below 15% of the boiler rating, replace the gas valve.

•

Note: Length of venting and combustion air piping will affect the measure boiler rating.

•

Check the ground lead for a secure connection from Control module ground to the burn-

er mounting plate. Use a ground continuity check to verify a good ground.

•

Remove the ignition electrode. Inspect for damage. Clean white oxides off the electrode.

Replace the electrode if damaged or will not clean.

E 03

Gas Valve Harness

•

Ensure gas valve rectifier cable is properly connected to the gas valve and secured.

•

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, replace the rectifier cable.

E 04

Loss of Power

Power to the boiler

is lost after a lockout

has occurred.

The boiler must be manually reset and the original lockout code will be lost.

•

Will also occur if the service technician tries to reset a hard lockout by turning the boiler

OFF and then ON as an attempt to reset the boiler.

•

Verify polarity and proper ground on incoming 120V power connections

•

May occur in rare cases if there is power interruption, surge or “Dirty” voltage. A relay kit is

available and may be installed on the incoming voltage to the boiler.

E 05

Internal Failure

Short in either the

ignition cable or dis-

play panel.

•

Check flat ribbon cable to display for short.

•

Check for moisture at display and repair cause of moisture, dry and/or replace display.

•

Inspect ignition cable replace if necessary.

•

Reset the boiler control module and retry ignition sequence and boiler operation.

•

If problem continues, contact AERCO International Technical Support for additional assis-

tance.

E 06

Internal Failure

•

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 07

Internal Failure

•

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 08

Internal Failure

•

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.