E 15, E 16, E 17 – AERCO Esteem O&M Manual User Manual

Page 87: E 18, E 19, E 24

Advertising
background image

81

GF-125

E 15

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 16

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 17

Internal Failure

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.

E 18

High Temperature

Limit, Supply

Temperature

Boiler supply water

temperature exceeds

212

ºF.

•

Check the following.

•

The boiler and heating system are filled with water and the LWCO is operating properly.

•

The boiler and heating system have been properly purged and there is no trapped air.

•

Inspect heating system piping and its components. Ensure piping is per the recommenda-

tions given in this Installation Manual or other approved design configurations.

•

Use a device to measure the supply water temperature leaving the boiler. Compare this

measured temperature with the display temperature (See page 52.)

•

Replace supply temperature sensor if temperature comparison is off by more than 10

ºF.

E 19

High Temperature

Limit, Return

Temperature

Boiler return water

temperature exceeds

212

ºF.

Check the following:

•

The boiler and heating system are filled with water and the LWCO is operating properly.

•

The boiler and heating system have been properly purged and there is no trapped air.

•

Inspect heating system piping and its components. Ensure piping is per the recommenda-

tions given in this manual or other approved design configurations.

•

Ensure boiler piping is correct and water flow is not reversed nor pipes cross-connected.

•

Use a device to measure the return water temperature leaving the boiler. Compare this

measured temperature with the display temperature (See page 52.)

•

Replace return temperature sensor if temperature comparison is off by more than 10

ºF

.

E 24

Low Voltage Internal

Short or Voltage

Feedback

Short or voltage

feedback in the 24V

circuit.

Check the following:

•

Line voltage to the boiler for polarity and 120VAC. Ensure the boiler is on a dedicated line. If

voltage is supplied from “OFF-GRID” source, check conditions.

•

Moisture on and around the low voltage terminal strip on the boiler. Resolve moisture issue.

•

Moisture on the display. Resolve moisture issue and replace the display panel.

•

Voltage feedback to Terminals 7 and 8, Terminals 11 and 12, and Terminals 17 and 18.

•

Remove all field wiring from the boiler and reset the boiler control module.

•

Initiate a call for heat external to the boiler and check for voltage on field wiring to termi-

nals 7 and 8 (space heating) and terminals 11 and 12 (DHW heating).

•

Reset the boiler control module and retry ignition sequence and boiler operation. If problem

continues, contact AERCO International Technical Support for additional assistance.