Chapter 18 maintenance procedures, Warning, Attend to reported problems – AERCO Esteem O&M Manual User Manual

Page 69: Check surrounding area, Inspect burner area, Check system piping, Gf-125

Advertising
background image

63

WARNING!

T

HE

E

STEEM

399 L

OW

NO

X

SHOULD

BE

IN

-

SPECTED

AND

SERVICED

ANNUALLY

,

PREFER

-

ABLY

AT

THE

START

OF

THE

HEATING

SEASON

,

BY

A

QUALIFIED

SERVICE

TECHNICIAN

. I

N

AD

-

DITION

,

THE

MAINTENANCE

AND

CARE

OF

THE

UNIT

AS

OUTLINED

ON

PAGE

62

AND

FURTHER

EXPLAINED

IN

THIS

CHAPTER

SHOULD

BE

PER

-

FORMED

TO

ASSURE

MAXIMUM

EFFICIENCY

AND

RELIABILITY

OF

THE

UNIT

. F

AILURE

TO

SERVICE

AND

MAINTAIN

THE

E

STEEM

399 L

OW

NO

X

AND

THE

SYSTEM

COMPONENTS

COULD

RESULT

IN

EQUIPMENT

FAILURE

,

CAUSING

POSSIBLE

SE

-

VERE

PERSONAL

INJURY

,

DEATH

OR

SUBSTAN

-

TIAL

PROPERTY

DAMAGE

.

N

OTICE

The following information provides de-
tailed instruction for completing the
maintenance items outline in the main-
tenance schedule on page 62. In addi-
tion to this maintenance, the Esteem
399 Low NOx should be serviced at the
beginning of the heating season by a
qualifi ed service technician.

Attend to Reported Problems

Any problems reported by the owner should
be checked, verified and corrected before
proceeding with any maintenance procedures.

Check Surrounding Area

Verify that the area surrounding the Esteem
399 Low NOx is free of combustible / flamma-
ble materials or flammable vapors or liquids.
Remove immediately if found.

Verify that combustion air inlet area is free of
any contaminates. Refer to the materials listed
on page 7 of this manual. If any of these prod-
ucts are in the area from which the unit takes
its combustion air, they must be removed
immediately or the combustion air intake must
be relocated to another area.

Inspect Burner Area

Remove the boiler front jacket panel and ven-
turi inlet elbow.

Vacuum any dirt or debris from the burner/
blower components.

Re-install venturi inlet elbow and front jacket
panel when completed.

WARNING!

D

O

NOT

USE

SOLVENTS

TO

CLEAN

ANY

OF

THE

BURNER

COMPONENTS

. T

HE

COMPONENTS

COULD

BE

DAMAGED

,

RESULTING

IN

UNRELIABLE

OR

UNSAFE

OPERATION

.

Check System Piping

Inspect all piping (water and gas) on the boiler
system for leaks and verify that the piping is
leak free and properly supported.

Inspect the fittings and components on the unit
and verify they are leak free.

WARNING!

E

LIMINATE

ALL

BOILER

WATER

SYSTEM

LEAKS

.

C

ONTINUAL

FRESH

MAKE

-

UP

WATER

WILL

RE

-

DUCE

THE

HEAT

EXCHANGER

LIFE

CAUSING

BOIL

-

ER

FAILURE

. L

EAKING

WATER

MAY

ALSO

CAUSE

SEVERE

PROPERTY

DAMAGE

TO

THE

SURROUND

-

ING

AREA

. I

NSPECT

THE

GAS

SUPPLY

PIPING

US

-

ING

THE

PROCEDURE

OUTLINED

ON

PAGE

40.

Chapter 18

Maintenance Procedures

GF-125

Advertising