Initial troubleshooting checks, Warning, 70 control module fuses – AERCO Esteem O&M Manual User Manual

Page 76: Control module fuses, Gf-125

Advertising
background image

70

Control Module Fuses

Initial Troubleshooting Checks

WARNING

L

ABEL

ALL

WIRES

AND

WIRE

CONNECTIONS

PRIOR

TO

DISCONNECTING

WHEN

SERVICING

ANY

BOILER

CON

-

TROLS

. W

IRING

ERRORS

CAN

CAUSE

IMPROPER

AND

DANGEROUS

OPERATION

. A

LWAYS

DISCONNECT

THE

POWER

SUPPLY

TO

THE

BOILER

BEFORE

SERVICING

. F

AILURE

TO

COMPLY

COULD

RESULT

IN

SEVERE

PER

-

SONAL

INJURY

,

DEATH

OR

SUBSTANTIAL

PROPERTY

DAMAGE

.

WARNING

N

EVER

BYPASS

(

JUMPER

)

ANY

BOILER

,

CONTROL

OR

DEVICE

EXCEPT

FOR

MOMENTARY

TESTING

WHEN

TROUBLESHOOTING

THE

BOILER

AS

OUTLINED

IN

THIS

GUIDE

,

SEVERE

PERSONAL

INJURY

,

DEATH

OR

SUB

-

STANTIAL

PROPERTY

DAMAGE

CAN

RESULT

.

• Ensure all wire connectors to the control module and sensors are securely connected.
• Ensure the maximum gas supply pressure does not exceed 13”w.c. during fl ow or no fl ow con-

ditions.

• Ensure the gas supply pressure is a minimum 5” w.c. during fl ow conditions (burner fi ring on all

gas appliances).

Control Module Fuses

N

OTICE

The control module contains 2 internal replaceable fuses. Ensure the fuses are in working
condition prior to replacing the control module or any boiler component. If one of the fuses
has blown, it will prevent the control module and/or boiler components from operating prop-
erly.

To check or replace the control module fuses:

1. Disconnect the external power supply to the boiler.
2. Remove the front jacket panel of the boiler by removing the thumb screw along the top edge.
3. Remove the electrical connectors at the MCBA control module for the igniter, transformer and

display (ribbon cable) and the black plastic housing cover off the control module. Use care
not to damage the cover when removing it.

4. Remove both fuses and check for continuity to determine if fuse is blown, replace if neces-

sary.

5. The control module is supplied from the factory with 2 spare fuses, a 5 amp fast acting fuse

and a 4 amp slow acting fuse, attached to the control module cover.

6. When replacing the fuses ensure the amp rating and type of the fuse matches the replace-

ment fuse. See Figure 27 on page 71, page 4 for amperage and location of the fuses.

WARNING

D

O

NOT

BYPASS

ANY

FUSE

WITH

A

JUMPER

. D

O

NOT

REPLACE

ANY

FUSE

WITH

A

FUSE

THAT

IS

NOT

SPECIFIED

. F

AILURE

TO

COMPLY

COULD

RESULT

IN

SEVERE

PERSONAL

INJURY

,

DEATH

OR

SUBSTAN

-

TIAL

PROPERTY

DAMAGE

.

GF-125