Table 10-4: BMM Fault Codes (Continued)

CODE DESCRIPTION

EFFECT

CORRECTION

RESET

14

Return Sensor

fault

All burners

turned OFF.

Check return sensor or

wiring.

AUTOMATIC

15

Maximum Δ-

temperature

protection.

Flow

temperature -

Return

Temperature >

Water Δ-Temp

Protection +

50°F

All burners

turned OFF

and Pump ON

at maximum

speed.

Check the system

installation.

AUTOMATIC -

when Δ-

temperature <

Water Δ-Temp

Protection.

16

Boiler Pipe is

frozen.

FlowSensor

temperature is

36°F or less.

Ignition is

inhibited. Pump

runs for 5 min

at max speed.

Carefully defrost boiler

AUTOMATIC -

when FlowSensor

is greater than

41°F.

20

Flame signal

detected after

burner is OFF.

Ignition is

inhibited.

Disconnect gas valve wire

from BMM. If failure goes

away, check wiring or

change BMM. If failure

remains check or change

gas valve.

MANUAL - push

reset switch or

cycle power.

22

No air flow at

burner after fan

started for 30

seconds.

Ignition retry

after 60 second

delay and

failure remains

until we have a

successful

burner

operation.

If fan is stopped, check

supply voltage and fan

wiring. If OK try another

fan. If still not working

change the BMM.

If fan is not stopped, check

the exhaust gas outlet for

blockage. If OK then check

the air pressure switch

wiring. If still not working try

another air pressure switch.

If still not working, change

the BMM.

AUTOMATIC/MAN

UAL

23

The air

pressure switch

doesn't switch

off.

Ignition is

inhibited.

Disconnect the air proving

switch. If problem goes

away install a new switch. If

not, check the wiring. If

wiring OK then change

BMM.

AUTOMATIC