7.3 BCM Configured as Back-Up Controller

When the BCM is configured as the Back-Up Controller for the E8, it will assume control of the

Modulex Boiler if the E8 fails. In the event of an E8 Controller failure, the BCM will operate the

Modulex Boiler in the Constant Setpoint Mode (default setpoint = 180°F [82°C]). The primary

Boiler Pump must also be wired to the BCM so it will run when the BCM assumes control in the

Back-Up Mode.
If a setpoint temperature lower than 180°F is desired, the setpoint can be changed prior to boiler

start-up. Refer to

paragraph 7.3.1 for details.

7.3.1 BCM Back-Up Controller Wiring

The Primary Boiler Pump must be wired to BCM Connector Y4 as shown in

Figure 7-4. Also, if

a Constant Setpoint temperature lower than the default setting of 180°F (82°C) is desired in the

event of an E8 failure, the appropriate resistor must be connected across terminals 6 and 7 of

BCM Connector Y2 as shown in

Figure 7-5.

Figure 7-4: BCM Back-Up Controller Wiring