Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Table 9-4: BCM Standard Holding Register Address Mapping (Continued)

Modbus Data

Address

Menu Item

Units and Range

Default/(Comments)

CONTROL REGISTERS (Continued)

1041

Check Mode,

Inserted burner

control

Flags

(0 – 0xFF)

Bit 0: BMM #0 to

Bit 7: BMM #7

(Read/Write)

Bit 0 (BMM #0) is auto-

matically set at Check

Mode start

OPERATING DATA REGISTERS

0

Error Code

0 – 0xFFFF

LSB: Error Code

MSB: Identification code

of fault device:

0: BMM #0 to

7: BMM #7

255: BCM

(Read Only)

1000

Cascade Control

Status

enum (0, 1, 2, 4)

0: Stop

1: Slave identification

procedure

2: Normal operation

4: Monitor mode

(Read Only)

1002

Flow Sensor

Temperature

14°F to 212°F

(-10°C to 100°C)

(Value x 10)

(Read Only)

1003

Return Flow

Temperature

32°F to 212°F (0°C to

100°C)

(Value x 10)

(Read Only)

1005

External Sensor

Temperature

-31°F/-22°F to 86°F

(-35°C/-30°C to 30°C)

(Value x 10)

(Read Only)

-31°F (-35°C) if not

connected

1008

Global Actual

Modulation Level

0 – 100%

(Read Only)

1016

Actual Target

Setpoint

32°F to 212°F (0°C to

100°C)

(Value x 10)

Should increase up to

“Target Setpoint” temp as

boiler heats up

(Read Only)

1018

Target Setpoint 32°F to 212°F (0°C to

100°C) (Value x 10)

(Read Only)

1019

DHW Maximum

Setpoint

32°F to 212°F (0°C to

100°C) (Value x 10)

(Read Only)