5.2.4.1 Configuring HEATSLOPE Parameter

The

HEATSLOPE value is configured as shown in the instructions below.

Configuring HEATSLOPE Parameter

1. Ensure ON/OFF switch on front of Modulex boiler is in the ON position.

2. Open controller front panel.

3. Turn the Rotary Knob clockwise to the USER menu.

4. Press Program Key to select the User submenu. The first item (sub-menu) displayed will

be

INSTALLATION.

5. Continue scrolling clockwise through the

USER menu until the HTG CIRCUIT 1 sub-menu

is displayed.

6. With

HTG CIRCUIT 1 displayed, press the Program Key to enter this sub-menu.

7. Using the Rotary Knob, scroll to the

HEATSLOPE variable. The display will show

HEATSLOPE” and the current value stored in memory (0.00 to 3.00).

8. If the desired value for

HEATSLOPE is not displayed, press the Program Key once. The

red LED will light.

9. Determine the required value for the

HEATSLOPE function as explained above. The

value to be entered must be between 0 and 3.00 inclusively.

10. Turn the Rotary Knob until the desired

HEATSLOPE value is displayed.

11. Press the Program Key to store the

HEATSLOPE value. The value will flash indicating it

was entered.

Continue scrolling through the

HTG CIRCUIT 1 sub-menu until RETURN is displayed.

Press the Program Key to exit the

HTG CIRCUIT 1 sub-menu.