3 configuring max t-col parameter, 3 0 to 10 volt remote set point mode, 1 remote signal source wiring connections – AERCO Modulex E8 Controls Guide User Manual

Page 47: Gf-115-c, Modulex e8 controller and bcm

Advertising
background image

PR1: 11/30/12

Page

47 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

5.2.4.3 Configuring MAX T-COL Parameter

To enter the MAX T-COL value, see instructions below.

Configuring MAX T-COLL Parameter

1. Set the ON/OFF switch on the front of the Modulex boiler to the ON position.

2. Open the swing-down hinged panel of the Controller.

3. Turn the Rotary Knob clockwise to the

EXPERT menu. The first item (sub-menu) displayed

will be

INSTALLATION.

4. The first sub-menu to be displayed will be

INSTALLATION.

5. Press the Program key once to enter this sub-menu.

6. Using the Rotary Knob, scroll to

MAX T-COLL. The display will show “MAX T-COLL” and

the current value stored in memory (86 to 230).

7. If the desired value for

MAX T-FLOW is not displayed, press the Program Key 6 times to go

through the digit sequence.

8. Now press the Program key one more time. The red LED will light.

9. Rotate the Rotary Knob until the desired value for

MAX T-COLL is displayed.

10. Press the Program Key once. The new value for

MAX T-COLL will flash indicating it was

entered.

11. Continue scrolling through the

INSTALLATION sub-menu until RETURN is displayed. Press

the Program Key to exit the

INSTALLATION sub-menu.

5.3 0 to 10 Volt Remote Set Point Mode

This mode allows the boiler set point to be controlled by an external control signal. The following

paragraphs provide the procedures necessary to wire, configure and set the required functions

necessary to operate in the 0 to 10 volt remote set point mode.

5.3.1 Remote Signal Source Wiring Connections

When setting up to operate in the 0 to 10 volt remote set-point mode, the remote signal source

must be wired to terminals 1 (F-15) and 2 (GND) of connector number 3 (III) on the rear of the

Controller. See

Section 6 for illustrations and pin-outs of the connectors located on the rear of

the Controller.




Advertising