Table 4-2: USER Menu Listing (Continued)

FUNCTION

DESCRIPTION

ENTRY RANGE

DEFAULT

HTG CIRCUIT 1 Sub-Menu

MODE

Displays Timer Mode for Boiler

- - - -, Standby,

Auto 1, Auto 2, Day,

Night

- - - -

T-ROOM DES 1

Not Applicable

T-ROOM DES 2

Not Applicable

T-ROOM DES 3

Not Applicable

T-REDUCED

Not Applicable

T-ABSENCE

Not Applicable

T-LIMIT DAY

Applies during day-time heating periods

- - - -,

-23.0°F–104.0°F

66.0°F

T-LIMIT N

Applies during reduced night-time

periods.

- - - -,

-23.0°F–104.0°F

50.0°F

HEATSLOPE

Indicate number of degrees that the flow

temperature changes if the outside

temperature increases or decreases by

1°F.

0.00 – 3.00

1.20

OPTIM HEAT

Not Applicable

MAX OPT-TIME

Not Applicable

ECONO OPTI

Not Applicable

PC-ENABLE

Not Applicable

RETURN

Press Program Key to exit HTG

CIRCUIT 1 (or 2) sub-menu.

HTG CIRCUIT 2 Sub-Menu

Functions for HTG Circuit 2 are identical to HTG Circuit 1 Functions listed above.

SOLAR M / F Sub-Menu (No Functions Currently In This Sub-Menu)

RETURN

Pressing the Program Key with SOLAR

M/F displayed will change display to

RETURN. Press Program Key again to

redisplay SOLAR M/F. Turning the

Rotary Knob clockwise will advance thd

display to the TIME PROGRAM Menu.