Page

38 of 112

GF-115-C

Modulex E8 Controller and BCM

Operations and Maintenance Manual

OMM-0084_0D

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526- 0288

Table 4-7: INSTALLATION Menu Listing

PARAMETERS

DESCRIPTION

ENTRY RANGE

DEFAULT

INSTALLATION Sub-Menu

LANGUAGE

Set Language

ENGLISH

TIME

Set current time (min., hrs)

00:00 – 24:00

YEAR

Set current year

XXXX (4 digits)

MONTH

Set current month

00-12

DAY

Set current day of month

00-31

CONF DEVICE

Confirm Device

- - - -, 01 – 06

- - - -

HEATSOURCE 1 Heat Source 1

00 – 06

06

HS1 BUS

Heat Source 1 Bus

00 – 04

02

HEATSOURCE 2

Heat Source 2

00 – 05

00

STORAGE HS2

Storage Heat Source 2

00 – 03

00

BUFFER

Buffer

00, 01, 02

00

HC FUNCTION 1

Heating Circuit Function 1

00, 01, 03

00

HC FUNCTION 2

Heating Circuit Function 2

00 – 04

00

CAP/MODULE

See

Paragraph 4.8.1 for instructions.

00 – 1000 Kw

40 Kw

RELAY FUNC 1

Relay Function 1 (See

Paragraph

4.8.2)

00 – 26

00

T-MF1 SETP

Temperature – Multifunction Relay 1

Setpoint

86°F – 194°F

86°F

MF1 HYST

Multifunction Relay 1 Hysteresis

4°F – 18°F

9°F

RELAY FUNC 2

Relay Function 2 (See

Paragraph

4.8.2)

00 – 26

00

T-MF2 SETP

Temperature – Multifunction Relay 2

Setpoint

86°F – 194°F

86°F

MF2 HYST

Multifunction Relay 2 Hysteresis

4°Ra – 18°Ra

9°F

RELAY FUNC 3

Relay Function 3

00 – 26

01

T-MF3 SETP

Temperature – Multifunction Relay 3

Setpoint

86°F – 194°F

86°F

MF3 HYST

Multifunction Relay 3 Hysteresis

4°F – 18°F

9°F

RELAY FUNC 4

Relay Function 4

00 – 26

02

T-MF4 SETP

Temperature – Multifunction Relay 4

Setpoint

86°F – 194°F

86°F

MF4 HYST

Multifunction Relay 4 Hysteresis

4°F – 18°F

9°F

BUS ID 1

Bus Identification No. 1

00 – 15

01

BUS ID 2

Bus Identification 2

00 – 15

02

5K SENSOR

5,000 Ohm Sensor

00=5K, 01=1K

00 = 5 K